OSHA SearchOSHA records by employer

Empire Electric, Inc.: OSHA inspections and violations

Riverview, Florida · Other Services to Buildings and Dwellings · NAICS 561790

2inspections
5citation items
$11,128current penalties
Dec 17, 2021last inspection

OSHA has inspected Empire Electric, Inc. 2 times in Florida since 2009.

The latest one began on Dec 17, 2021 on a referral, in Jacksonville.

Those inspections ended with 5 citation items: 5 serious.

Penalties were first proposed at $11,316 and now stand at $11,128, 2% lower after settlements or reviews.

Safeguards for personnel protection comes up most often in these citations: 3 items under 1910.335.

How that compares: the median penalty per cited inspection for staffing, cleaning and waste services employers since 2015 is $2,208, and Empire Electric, Inc. averages $10,566 (1 cited inspection).

Empire Electric, Inc.: OSHA citation items per year, 2009 to 2021
Citation items per year, by inspection date.

Florida · latest 90 days of OSHA records

326employers cited

Get notified the morning OSHA posts each new citation in Florida: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Florida

Checking a subcontractor, a client or your own company? Watch Empire Electric, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 345693212 OPENED DEC 17, 2021Closed

Referral · Partial · Safety · 24 employees at the site · Closed Aug 3, 2022

3269 University Blvd North, Jacksonville, FL 32277 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Dec 14, 2021: Two employees are burned in arc flash during breaker replace

At 5:00 p.m. on December 14, 2021, Employees #1 and #2 worked to troubleshoot and repair a live one hundred-ampere main breaker. Employee #1 removed the dead front panel and the old breaker and began to install the new one hundred ampere breaker. Employee #1 stood in front of the panel while working and had connected the new breaker to the A-phase side using a non-insulated flat tip screwdriver (KLEIN Tools Serial #32290) and began to line up the C-phase side when an arc flash fire ball shot out of the panel and engulfed both employees. Both employees were hospitalized to treat electrical burns. Employee #1 received second degree burns to the face, head, ears, and neck, and third degree burns to the left arm. Employee #2 received second degree burns to the face, neck, arm, and upper torso.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.333(a) · Working near live electrical parts
Serious$3,522$3,522Jun 9, 2022Final
Citation 1, item 2a
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$3,522$3,522Jun 9, 2022Final
Citation 1, item 2b
29 CFR 1910.335(a)(1)(v) · Safeguards for personnel protection
Serious$0$0Jun 9, 2022Final
Citation 1, item 3
29 CFR 1910.335(a)(2)(i) · Safeguards for personnel protection
Serious$3,522$3,522Jun 9, 2022Final

Inspection 313361859 OPENED MAY 14, 2009Closed

Planned · Partial · Safety · 2 employees at the site · Closed Aug 11, 2009

10433 Gibsonton Dr., Riverview, FL 33578 · Other Services to Buildings and Dwellings · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.67(c)(2)(v) · Vehicle-mounted elevating and rotating work platforms
Serious$750$562Jun 12, 2009Closed

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)

(a) General. Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1910.335(a)(1)(i)

(a) Use of protective equipment—(1) Personal protective equipment. (i) Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.

29 CFR 1910.335(a)(1)(v)

(v) Employees shall wear protective equipment for the eyes or face wherever there is danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion.

29 CFR 1910.67 · Vehicle-mounted elevating and rotating work platforms

Other other services to buildings and dwellings employers in Florida

Alert subscribers get notified of each newly cited employer in Florida the morning it is posted. See the alert plans.