Inspection 345693212 OPENED DEC 17, 2021Closed
3269 University Blvd North, Jacksonville, FL 32277 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps
Incident on Dec 14, 2021: Two employees are burned in arc flash during breaker replace
At 5:00 p.m. on December 14, 2021, Employees #1 and #2 worked to troubleshoot and repair a live one hundred-ampere main breaker. Employee #1 removed the dead front panel and the old breaker and began to install the new one hundred ampere breaker. Employee #1 stood in front of the panel while working and had connected the new breaker to the A-phase side using a non-insulated flat tip screwdriver (KLEIN Tools Serial #32290) and began to line up the C-phase side when an arc flash fire ball shot out of the panel and engulfed both employees. Both employees were hospitalized to treat electrical burns. Employee #1 received second degree burns to the face, head, ears, and neck, and third degree burns to the left arm. Employee #2 received second degree burns to the face, neck, arm, and upper torso.
| Citation and rule | Type | Proposed | Current | Issued | Status |
|---|---|---|---|---|---|
| Citation 1, item 1 29 CFR 1910.333(a) · Working near live electrical parts |
Serious | $3,522 | $3,522 | Jun 9, 2022 | Final |
| Citation 1, item 2a 29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection |
Serious | $3,522 | $3,522 | Jun 9, 2022 | Final |
| Citation 1, item 2b 29 CFR 1910.335(a)(1)(v) · Safeguards for personnel protection |
Serious | $0 | $0 | Jun 9, 2022 | Final |
| Citation 1, item 3 29 CFR 1910.335(a)(2)(i) · Safeguards for personnel protection |
Serious | $3,522 | $3,522 | Jun 9, 2022 | Final |