OSHA SearchOSHA records by employer

Empower Battery, LLC: OSHA inspections and violations

Martinsburg, West Virginia · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
3citation items
$0current penalties
Dec 4, 2018last inspection

OSHA has inspected Empower Battery, LLC once in West Virginia.

The inspection began on Dec 4, 2018 after a fatality or catastrophe, in Martinsburg.

That inspection ended with 3 citation items: 3 serious.

Penalties were first proposed at $13,260 and now stand at $0, 100% lower after settlements or reviews.

Working near live electrical parts comes up most often in these citations: 2 items under 1910.333.

How that compares: the median penalty per cited inspection for construction employers since 2015 is $3,080, and Empower Battery, LLC averages $0 (1 cited inspection).

1 inspection on this page followed a fatal incident.

Empower Battery, LLC: OSHA citation items per year, 2018 to 2018
Citation items per year, by inspection date.

West Virginia · latest 90 days of OSHA records

28employers cited

Get notified the morning OSHA posts each new citation in West Virginia: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in West Virginia

Checking a subcontractor, a client or your own company? Watch Empower Battery, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 343648713 OPENED DEC 4, 2018Closed

Fatality or catastrophe · Partial · Safety · 3 employees at the site · Closed Jun 4, 2020

221 Butler Ave Bldg 511, Martinsburg, WV 25405 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Dec 4, 2018 (fatal): Employee contacts dc batteries and is electrocuted

At 11:37 a.m. on December 4, 2018, an employee was replacing 640 batteries in the facilities uninterrupted power supply (UPS) room. The batteries were linked in 16 strings with each string having 40 batteries tied in series. Each string was 540V and 2280 amps. The employee reached overtop of a metal batter rack to retrieve a Styrofoam spacer and his abdomen came in contact with the string of batteries below. The employee was electrocuted.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.333(a)(2) · Working near live electrical parts
Serious$13,260$0May 20, 2019Final
Citation 1, item 1b
29 CFR 1910.333(c)(2) · Working near live electrical parts
Serious$0$0May 20, 2019Final
Citation 1, item 1c
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$0$0May 20, 2019Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(2)

(2) Energized parts. If the exposed live parts are not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices shall be used to protect employees who may be exposed to the electrical hazards involved. Such work practices shall protect employees against contact with energized circuit parts directly with any part of their body or indirectly through some other conductive object. The work practices that are used shall be suitable for the conditions under which the work is to be performed and for the voltage level of the exposed electric conductors or circuit parts. Specific work practice requirements are detailed in paragraph (c) of this section.

29 CFR 1910.333(c)(2)

(2) Work on energized equipment. Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1910.335(a)(1)(i)

(a) Use of protective equipment—(1) Personal protective equipment. (i) Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.

Other electrical contractors and other wiring installation contractors employers in West Virginia

Alert subscribers get notified of each newly cited employer in West Virginia the morning it is posted. See the alert plans.