OSHA SearchOSHA records by employer

Entech Sales and Service, LLC: OSHA inspections and violations

Dallas, Texas · Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance · NAICS 811310

4inspections
5citation items
$24,000current penalties
Aug 27, 2026last inspection

Entech Sales and Service, LLC has 4 OSHA inspections on record in Texas, the first in 1986.

OSHA's last visit started on Aug 27, 2026 on a referral, in Dallas, and the case has not closed yet.

Across those inspections OSHA issued 5 citation items: 5 serious.

OSHA proposed $45,464 in penalties. After settlements and reviews the total is $24,000, down 47%.

Most often, OSHA cited 1910.335, safeguards for personnel protection (3 items).

For context, across all repair and personal services employers the median penalty per cited inspection since 2015 is $1,200. Entech Sales and Service, LLC averages $24,000 over 1 cited inspection in that time.

Entech Sales and Service, LLC also files yearly injury logs with OSHA, summarized below.

It reported 1 severe injury to OSHA since 2015.

Entech Sales and Service, LLC: OSHA citation items per year, 1986 to 2026
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

399employers cited

5 of them in the same industry

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Entech Sales and Service, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 349138180 OPENED AUG 27, 2026Open

Referral · Partial · Safety · 117 employees at the site · Open

2201 N Main St, Dallas, TX 75201 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection so far.

Inspection 345073076 OPENED DEC 15, 2020Closed

Follow-up · Partial · Safety · 35 employees at the site · Closed Feb 22, 2021

8202 Sand Pebble, San Antonio, TX 78250 · Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 344223219 OPENED AUG 8, 2019Closed

Referral · Partial · Safety · 400 employees at the site · Closed Jan 31, 2020

8202 Sand Pebble, San Antonio, TX 78250 · Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance · OSHA's record · Phone and website on Google Maps

Incident on Aug 7, 2019: Two employees suffer third degree burns from an arc flash in

At 10:45 p.m. on August 7, 2019, Employee #1 was attempting to preform a load bank test to the building's automatic transfer switch panel connected to the back-up generator, by connecting the load bank test wires. An arc flash incident occurred, resulting in third degree burns to Employee #1 and Employee #2. The arc flash occurred as a result of not ensuring effective lockout/tagout completed prior to performing the load bank test on the generator. Neither employee had donned the appropriate arc flash PPE. Employee #1 sustained third degree burns to his hands, neck, face, ears, and upper arms requiring extended hospital treatment in the burn unit. Employee #2 sustained third degree burns to his hands, arms and forearms, and parts of the neck and face, as well as multiple strokes from the arc flash incident.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1 Serious$11,366$7,000Dec 26, 2019Final
Citation 1, item 2
29 CFR 1910.333(b)(2) · Working near live electrical parts
Serious$11,366$7,000Dec 26, 2019Final
Citation 1, item 3a
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$11,366$5,000Dec 26, 2019Final
Citation 1, item 3b
29 CFR 1910.335(a)(1)(v) · Safeguards for personnel protection
Serious$0$0Dec 26, 2019Final
Citation 1, item 4
29 CFR 1910.335(a)(2)(i) · Safeguards for personnel protection
Serious$11,366$5,000Dec 26, 2019Final

Inspection 100738269 OPENED OCT 21, 1986Closed

Referral · Partial · Safety · 2 employees at the site · Closed Nov 14, 1986

3662 W. Camp Wisdom Road, Dallas, TX 75006 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2025, the Dallas site logged 0 recordable injuries or illnesses among about 157 workers: 0.0 per 100 full-time workers, against a median of 1.5 for its industry.

Site and yearWorkersCasesDays-away casesRateIndustry median
Entech Sales & Service (Dallas)
Dallas · 2025
157 000.01.5
Dallas Office
Dallas · 2021
119 100.71.5

Included with any plan: 8 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.

See plans

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Aug 7, 2019, San Antonio: Hospitalization · electrical burns, unspecified · nonclassifiable

Two employees servicing an ATS terminal for a load bank test with a generator were exposed to an arc flash when opening the terminal cover. The employees suffered dermal burns.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.332 · Training

29 CFR 1910.332(b)(1)

(b) Content of training—(1) Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by §§ 1910.331 through 1910.335 that pertain to their respective job assignments.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(b)(2)

(2) The procedures also incorporate the requirements of paragraphs (b)(2)(iii)(D) and (b)(2)(iv)(B) of this section.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1910.335(a)(1)(i)

(a) Use of protective equipment—(1) Personal protective equipment. (i) Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.

Other commercial and industrial machinery and equipment (except automotive and electronic) repair and maintenance employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.