OSHA SearchOSHA records by employer

Global Subtation Services, Inc.: OSHA inspections and violations

Middle River, Maryland · Electric Power Generation · NAICS 221119

1inspections
5citation items
$5,325current penalties
Dec 21, 2016last inspection

Global Subtation Services, Inc. has one OSHA inspection on record in Maryland.

OSHA opened it on Dec 21, 2016 after an accident, in Middle River.

From that inspection OSHA issued 5 citation items: 5 serious.

OSHA proposed $10,650 in penalties. After settlements and reviews the total is $5,325, down 50%.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (5 items).

For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Global Subtation Services, Inc. averages $5,325 over 1 cited inspection in that time.

Global Subtation Services, Inc.: OSHA citation items per year, 2016 to 2016
Citation items per year, by inspection date.

Maryland · latest 90 days of OSHA records

189employers cited

Get notified the morning OSHA posts each new citation in Maryland: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Maryland

Checking a subcontractor, a client or your own company? Watch Global Subtation Services, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 341989689 OPENED DEC 21, 2016Closed

Accident · Partial · Safety · 3 employees at the site · Closed May 11, 2017

2800 Eastern Blvd., Middle River, MD 21220 · Electric Power Generation · OSHA's record · Phone and website on Google Maps

Incident on Dec 21, 2016: Two employees are injured during electrical work

At 11:20 a.m. on December 21, 2016, Employees # 1 and #2 were replacing fuses in a switch gear cubicle. While standing on a ladder, Employee #1 came into contact with live exposed parts, resulting in him suffering second and third degree burns to over 40 percent of his body from arc flash burns. Employee #2 observed the incident and reacted by knocking Employee #1 from the ladder to release him from contact with the live part. This caused Employee#2 to receive an electrical shock and permanent damage to one of his hands. Both Employees #1 and #2 were hospitalized and treated for their injuries sustained. sustained.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(a)(2)(i)(a) · Electric power generation, transmission, and distribution
Serious$2,400$1,200Mar 30, 2017Final
Citation 1, item 2
29 CFR 1910.269(a)(2)(iv) · Electric power generation, transmission, and distribution
Serious$2,550$1,275Mar 30, 2017Final
Citation 1, item 3
29 CFR 1910.269(l)(8)(v) · Electric power generation, transmission, and distribution
Serious$900$450Mar 30, 2017Final
Citation 1, item 4
29 CFR 1910.269(m)(3)(ii) · Electric power generation, transmission, and distribution
Serious$2,400$1,200Mar 30, 2017Final
Citation 1, item 5
29 CFR 1910.269(n)(2) · Electric power generation, transmission, and distribution
Serious$2,400$1,200Mar 30, 2017Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(2)(i)(a)

(A) Each employee shall be trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments.

29 CFR 1910.269(a)(2)(iv)

(iv) The employer shall determine, through regular supervision and through inspections conducted on at least an annual basis, that each employee is complying with the safety-related work practices required by this section.

29 CFR 1910.269(l)(8)(v)

(v) The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm 2. This protective equipment shall cover the employee's entire body, except as follows:

Other electric power generation employers in Maryland

Alert subscribers get notified of each newly cited employer in Maryland the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.