OSHA has inspected Hutchinson Technology Inc 21 times in Minnesota since 1983.
The latest one began on Jul 6, 2017 after a complaint, in Hutchinson.
Those inspections ended with 31 citation items: 11 serious and 20 other-than-serious.
Penalties were first proposed at $15,725 and now stand at $12,968, 18% lower after settlements or reviews.
Electrical wiring methods comes up most often in these citations: 5 items under 1910.305.
How that compares: the median penalty per cited inspection for manufacturing employers since 2015 is $3,600, and Hutchinson Technology Inc averages $122 (1 cited inspection).
Hutchinson Technology Inc also files yearly injury logs with OSHA, summarized below.
Citation items per year, by inspection date.
Minnesota · latest 90 days of OSHA records
369employers cited
Get notified the morning OSHA posts each new citation in Minnesota: the employer, the site address, the rules broken and the penalty.
Incident on Apr 7, 2008: Five employees are exposed to chemical spill
On April 7, 2008, Employee #1, a chemical technician was filling chemical orders in the West Chemical Storage Room for use in other parts of the facility. He mi stakenly mixed hydrogen peroxide and hydrochloric acid. He then capped the conta iner containing the inadvertent mixture; stepped away from the cart to rinse his funnel in a sink; and, upon returning, noticed a discoloration of the liquid in the container. He recognized his error, realized that a chemical reaction was u nderway in the capped container, and attempted to transfer the offending contain er to another area using a cart. Upon rounding a corner at a hallway intersectio n referred to as the crossroads, the container rolled off of the cart, split alo ng one side from top to bottom, and spilled the majority of its contents. Employ ee #1 immediately started to clean up the spill using absorbent pads. The locati on where the container split was immediately outside of a room that contained a Zellweger System 16 gas detection system. At the time of the spill, the room's d oor was open and a portion of the spilled material entered the room. Gas from th e event caused staining of the system tape and triggered a Chlorine alarm in sev eral remote basement locations. There was no sampling port in the room containin g the system because a chlorine spill was not expected at that location. The Chl orine alarm triggered an evacuation of the basement and a call for the hazmat te am to report to the crossroads. Upon reporting to the crossroads, the team disco vered that the crossroads was the location of the incident and that a cleanup wa s already in progress. Team members left for a nearby storage area, donned SCBAs , and returned to check the area for victims. Employees #1, #2, #3, #4 and #5 we re transported to the Hutchinson Hospital for observation, but were treated and released.
From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.
In 2025, the Hutchinson site logged 0 recordable injuries or illnesses among about 29 workers: 0.0 per 100 full-time workers, against a median of 0.0 for its industry.
Site and year
Workers
Cases
Days-away cases
Rate
Industry median
Hutchinson Technology Inc. - Hutchinson, MN
Hutchinson · 2025
29
0
0
0.0
0.0
Included with any plan: 8 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.
(2) Design, construction, and capacity of containers—(i) General. Only approved containers and portable tanks shall be used. Metal containers and portable tanks meeting the requirements of and containing products authorized by chapter I, title 49 of the Code of Federal Regulations (regulations issued by the Hazardous Materials Regulations Board, Department of Transportation), shall be deemed to be acceptable.
29 CFR 1910.106(g)(3)(ivd)
(iv) Dispensing units. (a) Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be transferred from tanks by means of fixed pumps so designed and equipped as to allow control of the flow and to prevent leakage or accidental discharge.
29 CFR 1910.120 · Hazardous waste operations and emergency response
29 CFR 1910.120(q)(2)
(2) Attendance should be required at all training modules, with successful completion of exercises and a final written or oral examination with at least 50 questions.
29 CFR 1910.132 · Personal protective equipment, general requirements
Alert subscribers get notified of each newly cited employer in Minnesota the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.