OSHA SearchOSHA records by employer

JO-Carroll Energy, Inc. (NFP): OSHA inspections and violations

Albany, Illinois · Electric Power Distribution · NAICS 221122

1inspections
1citation items
$5,000current penalties
Jun 7, 2018last inspection

OSHA inspectors have visited JO-Carroll Energy, Inc. (NFP) in Illinois one time.

It opened on Jun 7, 2018 on a referral, in Albany.

In all, OSHA issued 1 citation item: 1 serious.

The proposed penalties came to $6,467; today they stand at $5,000, 23% less.

Among utility employers, the typical cited inspection since 2015 ends with a $0 penalty. JO-Carroll Energy, Inc. (NFP) averages $5,000 across 1 cited inspection.

It reported 1 severe injury to OSHA since 2015.

JO-Carroll Energy, Inc. (NFP): OSHA citation items per year, 2018 to 2018
Citation items per year, by inspection date.

Illinois · latest 90 days of OSHA records

414employers cited

Get notified the morning OSHA posts each new citation in Illinois: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Illinois

Checking a subcontractor, a client or your own company? Watch JO-Carroll Energy, Inc. (NFP) and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 343212932 OPENED JUN 7, 2018Closed

Referral · Partial · Safety · 85 employees at the site · Closed Nov 21, 2018

2939 Palmar Rd, Albany, IL 61230 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Jun 4, 2018: Employee suffers electric shock while conducting power facto

At 1:40 p.m. on June 4, 2018, an employee was working for a rural electric power distribution cooperative. He and a coworker were at a substation in Albany, IL. They were performing a power factor test on a transformer. They were using a Megger DELTA2000 10kV Automated Insulation Power Factor Test Set to test the transformer's porcelain bushings for conductivity. The employee was at the transformer. His coworker was inside a nearby trailer, operating the equipment. This was a scheduled maintenance task that the lead employee had accomplished before. The narrative did not say whether the employee or his coworker was the lead employee. Two safety switches were provided and installed on the Megger Delta2000 10 kV Automated Insulation Power Factor Test Set. One switch was for the operator. The other switch was for the person conducting the tests at the bushings. The safety switch that was supposed to be for the tester had been bypassed and left inside the trailer with the tester's operator. The switch's button had been taped down with electrical tape and bypassed. This way, one worker could perform the test; it would not be necessary for there to be a second worker to hold down the other button. The employee and his coworker were not in each other's line of sight. They did have audio communications. The employee, who was testing the bushings for conductivity, was not required to wear electrically-rated gloves to protect against electric shock. During the test, the operator, who was inside the trailer, took a phone call. When the call was over a few minutes later, he started the testing again. The communication broke down. When he tried, verbally, to start the testing again, the employee, at the transformer, was confused as to what the verbal cues were for. The employee touched a live part. He sustained an electric shock. A call was placed to emergency medical services. Emergency personnel arrived to treat the employee. He was hospitalized. hospitalized.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(o)(6)(ii) · Electric power generation, transmission, and distribution
Serious$6,467$5,000Oct 2, 2018Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Jun 4, 2018, Albany: Hospitalization · electrical burns, unspecified · nonclassifiable

An employee was testing electrical equipment with an automated insulation test set and went to grab it and receive and was shocked. The employee sustained electrical burns.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(o)(6)(ii)

(ii) The test operator in charge shall conduct these routine safety checks before each series of tests and shall verify at least the following conditions:

Other electric power distribution employers in Illinois

Alert subscribers get notified of each newly cited employer in Illinois the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.