OSHA SearchOSHA records by employer

Liberty Utilities (Granite State Electric) Corp.: OSHA inspections and violations

Lebanon, New Hampshire · Electric Power Distribution · NAICS 221122

2inspections
4citation items
$39,313current penalties
Jul 1, 2022last inspection

OSHA has inspected Liberty Utilities (Granite State Electric) Corp. 2 times in New Hampshire since 2020.

The latest one began on Jul 1, 2022 on a referral, in Londonderry.

Those inspections ended with 4 citation items: 4 serious.

Penalties were first proposed at $54,984 and now stand at $39,313, 29% lower after settlements or reviews.

Electric power generation, transmission, and distribution comes up most often in these citations: 3 items under 1910.269.

How that compares: the median penalty per cited inspection for utility employers since 2015 is $0, and Liberty Utilities (Granite State Electric) Corp. averages $19,656 (2 cited inspections).

Liberty Utilities (Granite State Electric) Corp.: OSHA citation items per year, 2020 to 2022
Citation items per year, by inspection date.

New Hampshire · latest 90 days of OSHA records

55employers cited

Get notified the morning OSHA posts each new citation in New Hampshire: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in New Hampshire

Checking a subcontractor, a client or your own company? Watch Liberty Utilities (Granite State Electric) Corp. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 346057052 OPENED JUL 1, 2022Closed

Referral · Partial · Safety · 450 employees at the site · Closed Mar 28, 2023

15 Buttrick Road, Londonderry, NH 03053 · Fossil Fuel Electric Power Generation · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
OSH Act Section 5(a)(1) · General Duty Clause
Serious$14,502$12,325Dec 27, 2022Final

Inspection 344663851 OPENED FEB 27, 2020Closed

Referral · Partial · Safety · 50 employees at the site · Closed Sep 14, 2020

407 Miracle Mile, Lebanon, NH 03756 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Feb 27, 2020: Employee sustains shock while testing equipment, ribs fractu

On February 27, 2020, an employee working as an electrical installation and repair technician was testing a recloser in the shop of a power distribution company. The electrical panel had been mis-wired by a coworker causing power to be sent to a transformer on a piece of equipment that normally would not be powered. The employee was shocked while performing the work causing his heart to momentarily stop. Coworkers performed CPR and used a defibrillator on the employee until EMTs arrived and transported the employee to a medical center. The employee was hospitalized to treat several broken ribs caused by the CPR.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.269(a)(2)(v)(b) · Electric power generation, transmission, and distribution
Serious$13,494$13,494Jul 10, 2020Final
Citation 1, item 1b
29 CFR 1910.269(c)(1)(ii) · Electric power generation, transmission, and distribution
Serious$13,494$0Jul 10, 2020Final
Citation 1, item 3
29 CFR 1910.269(o)(3)(i) · Electric power generation, transmission, and distribution
Serious$13,494$13,494Jul 10, 2020Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(2)(v)(b)

(B) If new technology, new types of equipment, or changes in procedures necessitate the use of safety-related work practices that are different from those which the employee would normally use, or

29 CFR 1910.269(c)(1)(ii)

(ii) The employer shall ensure that the employee in charge conducts a job briefing that meets paragraphs (c)(2), (c)(3), and (c)(4) of this section with the employees involved before they start each job.

29 CFR 1910.269(o)(3)(i)

(3) Safeguarding of test areas. (i) The employer shall provide safeguarding within test areas to control access to test equipment or to apparatus under test that could become energized as part of the testing by either direct or inductive coupling and to prevent accidental employee contact with energized parts.

OSH Act Section 5 · General Duty Clause

Other electric power distribution employers in New Hampshire

Alert subscribers get notified of each newly cited employer in New Hampshire the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.