OSHA SearchOSHA records by employer

Lighting Maintenance Incorporated: OSHA inspections and violations

Fairfax, Virginia · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

5inspections
8citation items
$14,270current penalties
Sep 4, 2019last inspection

Since 2002, OSHA inspectors have visited Lighting Maintenance Incorporated in Virginia 5 times.

The most recent inspection opened on Sep 4, 2019 as a planned inspection, in Henrico.

In all, OSHA issued 8 citation items: 7 serious and 1 other-than-serious.

The proposed penalties came to $24,070; today they stand at $14,270, 41% less.

The rule cited most here is 1910.335 (safeguards for personnel protection), 2 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. Lighting Maintenance Incorporated averages $13,370 across 1 cited inspection.

1 inspection on this page followed a fatal incident.

Lighting Maintenance Incorporated: OSHA citation items per year, 2002 to 2019
Citation items per year, by inspection date.

Virginia · latest 90 days of OSHA records

253employers cited

7 of them in the same industry

Get notified the morning OSHA posts each new citation in Virginia: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Virginia

Checking a subcontractor, a client or your own company? Watch Lighting Maintenance Incorporated and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344280540 OPENED SEP 4, 2019Closed

Planned · Partial · Safety · 3 employees at the site · Closed Sep 10, 2019

9004 West Broad Street, Henrico, VA 23228 · Consumer Electronics Repair and Maintenance · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 340342518 OPENED FEB 9, 2015Closed

Fatality or catastrophe · Partial · Safety · 3 employees at the site · Closed Jun 19, 2018

Northbound 95 Exit 169 A, Springfield, VA 22150 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Feb 9, 2015 (fatal): Employee was killed from an electric shock while prepping an

At 2:15 p.m. on February 9, 2015 an employee working as a maintenance contractor for VDOT when he sustained a 277 volt electrical current which killed him. The employee and coworker were working on light poles that were not operational on Northbound I95 at exit 169A Springfield, VA. One coworker was at the disconnect that supplied power to the junction boxes and pole lights that is located approximately one minute away, behind a dealership inside panel 199. The employee was prepping a conductor to splice together at the junction box by pole # 011. The coworker at the disconnect, hooked up a shot box used to find faults in conductors, and proceeded to turn the power back on to the junction box that the employee was working in. Another coworker was writing a report in his truck when he looked over and saw the employee laying over the junction box and not responsive. The employee and coworker at the disconnect were not in eye sight of one another, and they were using cell phones to communicate with each other. phones to communicate with each other.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 2
29 CFR 1910.151(b) · First aid and eyewash
Other-than-serious$1,470$1,470Aug 6, 2015Final
Citation 1, item 3
29 CFR 1910.303(b)(2) · Electrical equipment, general requirements
Serious$2,450$2,450Aug 6, 2015Final
Citation 1, item 4a
29 CFR 1910.333(b)(2)(v)(b) · Working near live electrical parts
Serious$7,000$7,000Aug 6, 2015Final
Citation 1, item 4c
29 CFR 1910.333(b)(2)(ii)(b) · Working near live electrical parts
Serious$7,000$0Aug 6, 2015Final
Citation 1, item 5a
29 CFR 1910.335(a)(2)(i)(a) · Safeguards for personnel protection
Serious$2,450$2,450Aug 6, 2015Final
Citation 1, item 5b
29 CFR 1910.335(a)(2)(ii) · Safeguards for personnel protection
Serious$2,450$0Aug 6, 2015Final

Inspection 313638447 OPENED AUG 12, 2009Closed

Referral · Complete · Safety · 1 employee at the site · Closed Oct 2, 2009

Vdot, Hague Area Headquarters, Rt. 202, Hague, VA 22469 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.416(a)(1) · Electrical safety in construction
Serious$875$525Sep 14, 2009Closed

Inspection 307362665 OPENED JUN 25, 2004Closed

Planned · Partial · Safety · 2 employees at the site · Closed Aug 4, 2004

East Bound 66 At The Nutley Street Exit, Vienna, VA 22027 · Other Services to Buildings and Dwellings · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 305669988 OPENED NOV 20, 2002Closed

Planned · Partial · Safety · 1 employee at the site · Closed Feb 19, 2003

13960 Lee Highway, Fairfax, VA 22030 · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.453(b)(2)(v) · Aerial lifts
Serious$375$375Nov 26, 2002Closed

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.151 · First aid and eyewash

29 CFR 1910.151(b)

(b) In the absence of an infirmary, clinic, or hospital in near proximity to the workplace which is used for the treatment of all injured employees, a person or persons shall be adequately trained to render first aid. Adequate first aid supplies shall be readily available.

29 CFR 1910.303 · Electrical equipment, general requirements

29 CFR 1910.303(b)(2)

(2) Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(b)(2)(ii)(b)

(B) The circuits and equipment to be worked on shall be disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1926.416 · Electrical safety in construction

29 CFR 1926.453 · Aerial lifts

Other electrical contractors and other wiring installation contractors employers in Virginia

Alert subscribers get notified of each newly cited employer in Virginia the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.