OSHA SearchOSHA records by employer

Lovett Electrical Services, LLC: OSHA inspections and violations

Franklin, Texas · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

1inspections
4citation items
$6,968current penalties
May 24, 2022last inspection

OSHA inspectors have visited Lovett Electrical Services, LLC in Texas one time.

It opened on May 24, 2022 after a fatality or catastrophe, in Franklin.

In all, OSHA issued 4 citation items: 2 serious and 2 other-than-serious.

The penalties, $6,968 in total, stand where OSHA first set them.

The rule cited most here is 1903.19 (proving cited hazards were fixed), 2 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. Lovett Electrical Services, LLC averages $6,968 across 1 cited inspection.

1 inspection on this page followed a fatal incident.

Lovett Electrical Services, LLC: OSHA citation items per year, 2022 to 2022
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

393employers cited

7 of them in the same industry

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Lovett Electrical Services, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 345986319 OPENED MAY 24, 2022Closed

Fatality or catastrophe · Partial · Safety · 5 employees at the site · Closed Jul 17, 2025

7214 East Highway 79, Franklin, TX 77856 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on May 23, 2022 (fatal): Employee is electrocuted and falls from ladder

At 10:30 a.m. on May 23, 2022, an employee and a coworker were replacing two industrial lights with LED lights which were positioned approximately ten feet above the concrete floor. Rather than use the lockout/tagout procedures mandated by the company and the facility's protocol, the employees chose to bypass the procedures and just turn off breakers. However, the employees were not able to identify the correct breakers so the employee continued to work while the coworker took a smoke break. While the employee was wiring the LED industrial light on a ten foot Rock River ladder, he made contact with live electrical part, was electrocuted, fell from the ladder and was pronounced dead at the scene.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1 Serious$3,108$3,108Sep 14, 2022Final
Citation 1, item 2
29 CFR 1910.333(b)(2)(i) · Working near live electrical parts
Serious$3,108$3,108Sep 14, 2022Final
Citation 2, item 1
29 CFR 1903.19(c)(1) · Proving cited hazards were fixed
Other-than-serious$376$376Jul 3, 2023Final
Citation 2, item 2
29 CFR 1903.19(d)(1) · Proving cited hazards were fixed
Other-than-serious$376$376Jul 3, 2023Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1903.19 · Proving cited hazards were fixed

29 CFR 1903.19(c)(1)

(c) Abatement certification. (1) Within 10 calendar days after the abatement date, the employer must certify to OSHA (the Agency) that each cited violation has been abated, except as provided in paragraph (c)(2) of this section.

29 CFR 1903.19(d)(1)

(d) Abatement documentation. (1) The employer must submit to the Agency, along with the information on abatement certification required by paragraph (c)(3) of this section, documents demonstrating that abatement is complete for each willful or repeat violation and for any serious violation for which the Agency indicates in the citation that such abatement documentation is required.

29 CFR 1910.332 · Training

29 CFR 1910.332(b)(1)

(b) Content of training—(1) Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by §§ 1910.331 through 1910.335 that pertain to their respective job assignments.

29 CFR 1910.333 · Working near live electrical parts

Other electrical contractors and other wiring installation contractors employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.