OSHA SearchOSHA records by employer

Matrix Service Industrial Contractors, Inc.: OSHA inspections and violations

Philadelphia, Pennsylvania · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
7citation items
$28,000current penalties
Sep 29, 2015last inspection

Matrix Service Industrial Contractors, Inc. has 2 OSHA inspections on record in Pennsylvania, the first in 2011.

OSHA's last visit started on Sep 29, 2015 on a referral, in Camp Hill.

Across those inspections OSHA issued 7 citation items: 7 other-than-serious.

OSHA proposed $28,000 in penalties and the amount has not been reduced.

Most often, OSHA cited 1926.959, mechanical equipment (2 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Matrix Service Industrial Contractors, Inc. averages $28,000 over 1 cited inspection in that time.

1 inspection on this page followed a fatal incident.

It reported 1 severe injury to OSHA since 2015.

Matrix Service Industrial Contractors, Inc.: OSHA citation items per year, 2011 to 2015
Citation items per year, by inspection date.

Pennsylvania · latest 90 days of OSHA records

274employers cited

4 of them in the same industry

Get notified the morning OSHA posts each new citation in Pennsylvania: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Pennsylvania

Checking a subcontractor, a client or your own company? Watch Matrix Service Industrial Contractors, Inc. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 340988922 OPENED SEP 29, 2015Closed

Referral · Partial · Safety · 2,200 employees at the site · Closed Aug 30, 2016

2998 Glenwood Road, Camp Hill, PA 17011 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.950(c)(2)(i) · Electric Power Transmission and Distribution: general
Other-than-serious$7,000$7,000Mar 15, 2016Final
Citation 1, item 1b
29 CFR 1926.952(a)(1) · Job briefing
Other-than-serious$0$0Mar 15, 2016Final
Citation 1, item 1c
29 CFR 1926.952(b) · Job briefing
Other-than-serious$0$0Mar 15, 2016Final
Citation 1, item 2a
29 CFR 1926.959(d)(2) · Mechanical equipment
Other-than-serious$7,000$7,000Mar 15, 2016Final
Citation 1, item 2b
29 CFR 1926.959(d)(3)(iii) · Mechanical equipment
Other-than-serious$0$0Mar 15, 2016Final
Citation 1, item 3
29 CFR 1926.960(c)(1)(i) · Working on or near exposed energized parts
Other-than-serious$7,000$7,000Mar 15, 2016Final
Citation 1, item 4
29 CFR 1926.966(f)(1) · Substations
Other-than-serious$7,000$7,000Mar 15, 2016Final

Inspection 314235334 OPENED JUN 23, 2011Closed

Accident · Partial · Safety · 50 employees at the site · Closed Sep 30, 2011

2600 Christian Street, Philadelphia, PA 19148 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Jun 23, 2011 (fatal): Employee is fatally struck by a crane's falling load block

On June 23, 2011, Employee #1 working for an electrical subcontractor was assist ing Employee #2, the crane operator in the movement of a gang box (owned by the electrical subcontractor) via a permanently installed overhead bridge crane. The crane had two hoists (80 ton Main Hoist (MH) & 10 ton Auxiliary Hoist (AH)). Th e crane was remote controlled. The crane's MH was being used to lower the gang b ox to a different level. Employee #1 was assisting Employee #2 in the rigging of the gang box and connecting it to the MH load block's hook. Employee #2 briefly operated the AH controller thinking he was actuating the MH controller on the r emote control box. Employee #2 then moved his hand over to the MH controller and raised the gang box several feet so it could pass over an adjacent guardrail. P rior to the crane moving the gang box horizontally, a loud noise was heard from above. Subsequently the AH load block assembly became separated from its wire ro pe load line and came crashing down striking Employee #1 who was standing direct ly under it. This AH load block weighed 231 pounds and free fell approximately 3 5 feet. The AH upper limit switch assembly did not function to prevent the two-b lock condition. Two-blocking occurs when the hoist block comes into contact with a structural component of the crane's trolley assembly and ultimately causing t he hoist's wire rope to break. The AH upper limit switch was not tested for prop er operation prior to use. The crane was not used daily. Employee #2 was an empl oyee of the company who owned the crane. Employee #1 died from his injuries.

No citations from this inspection.

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Sep 28, 2015, Camp Hill: Hospitalization · electrical burns, unspecified · nonclassifiable

An employee was in an aerial lift approximately 8 feet high in an energized zone. The employee made contact with a station transformer, causing an arc flash, and was hospitalized.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.950 · Electric Power Transmission and Distribution: general

29 CFR 1926.950(c)(2)(i)

(2) Contract employer responsibilities. (i) The contract employer shall ensure that each of its employees is instructed in the hazardous conditions relevant to the employee's work that the contract employer is aware of as a result of information communicated to the contract employer by the host employer under paragraph (c)(1) of this section.

29 CFR 1926.952 · Job briefing

29 CFR 1926.952(a)(1)

(a) Before each job—(1) Information provided by the employer. In assigning an employee or a group of employees to perform a job, the employer shall provide the employee in charge of the job with all available information that relates to the determination of existing characteristics and conditions required by § 1926.950(d).

29 CFR 1926.952(b)

(b) Subjects to be covered. The briefing shall cover at least the following subjects: Hazards associated with the job, work procedures involved, special precautions, energy-source controls, and personal protective equipment requirements.

29 CFR 1926.959 · Mechanical equipment

29 CFR 1926.960 · Working on or near exposed energized parts

29 CFR 1926.966 · Substations

Other electrical contractors and other wiring installation contractors employers in Pennsylvania

Alert subscribers get notified of each newly cited employer in Pennsylvania the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.