OSHA SearchOSHA records by employer

MDR Construction, Inc.: OSHA inspections and violations

Seminary, Mississippi · Power and Communication Line and Related Structures Construction · NAICS 237130

6inspections
4citation items
$29,502current penalties
Oct 13, 2022last inspection

MDR Construction, Inc. has 6 OSHA inspections on record in Mississippi, the first in 2001.

OSHA's last visit started on Oct 13, 2022 on a referral, in Biloxi.

Across those inspections OSHA issued 4 citation items: 1 serious and 3 other-than-serious.

OSHA proposed $31,938 in penalties. After settlements and reviews the total is $29,502, down 8%.

Most often, OSHA cited 1926.960, working on or near exposed energized parts (2 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. MDR Construction, Inc. averages $12,251 over 2 cited inspections in that time.

2 inspections on this page followed a fatal incident.

It reported 2 severe injuries to OSHA since 2015.

MDR Construction, Inc.: OSHA citation items per year, 2001 to 2022
Citation items per year, by inspection date.

Want to know if OSHA cites MDR Construction, Inc. again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 346288608 OPENED OCT 13, 2022Closed

Referral · Partial · Safety · 802 employees at the site · Closed May 8, 2023

9192 Woolmarket Rd., Biloxi, MS 39532 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(l)(3)(iii) · Electric power generation, transmission, and distribution
Other-than-serious$10,436$10,000Apr 10, 2023Final

Inspection 345997720 OPENED MAY 25, 2022Closed

Referral · Partial · Safety · 800 employees at the site · Closed Apr 6, 2023

230 Dodd Rd, Sunflower, MS 38778 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.960(c)(1)(iii) · Working on or near exposed energized parts
Other-than-serious$14,502$14,502Oct 28, 2022Final
Citation 1, item 1b
29 CFR 1926.960(c)(2)(i)(a) · Working on or near exposed energized parts
Other-than-serious$0$0Oct 28, 2022Final

Inspection 340584754 OPENED APR 21, 2015Closed

Referral · Partial · Safety · 6 employees at the site · Closed Jun 29, 2015

2520 5th Street North, Columbus, MS 39701 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 337346019 OPENED NOV 8, 2012Closed

Follow-up · Complete · Safety · 90 employees at the site · Closed Nov 14, 2012

621 E. Baylis Chapel Road, Seminary, MS 39479 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 315306407 OPENED JAN 4, 2012Closed

Accident · Complete · Safety · 77 employees at the site · Closed Aug 3, 2012

466 Shirley Sanford Road, Seminary, MS 39479 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

Incident on Jan 4, 2012 (fatal): Employee is killed by electrocution

On January 4, 2012, Employee # 1 was working as a Journeyman Lineman. He lifted a 59 inch long armor-rod up out of his bucket and pass it (slide it) along the n ew field phase over to his coworker in another bucket on the South side of a C-2 -2 configured pole. Employee # 1 was electrocuted when the armor-rod contacted t he old energized conductor. Plus the employee was not wearing insulating gloves.

No citations from this inspection.

Inspection 304310410 OPENED JUL 11, 2001Closed

Accident · Complete · Safety · 120 employees at the site · Closed Feb 1, 2002

Highway 61 North, Valley Park, MS 39177 · OSHA's record · Phone and website on Google Maps

Incident on Jul 10, 2001 (fatal): Burn - electrical fault on overhead power line

A four-employee power line crew was working on a 13.2-kilovolt (7.62-kilovolt-to -ground) overhead power line. The crew was setting a new 12.2-meter-tall utility pole between two existing poles to take remove slack from a 120-meter span. A p ower line worker on the crew had elevated the three conductors, with the road-si de phase conductor tied to a winch behind him, the center phase conductor lying across the top of his aerial lift bucket, and the last phase conductor lying in a jib about a meter in front of the bucket. He had placed 2 lengths of 1.8-meter -long rubber insulating line hose on the road-side phase conductor and 1 length on each of the other two conductors. After the new pole was set, the power line worker had released the conductors. He positioned his aerial lift bucket between the road-side and center phase conductors on the north side of the new pole. Th e power line worker had four armor rods, a tool board filled with hand tools, an d coils of tie wire in the bucket with him. The crew supervisor was on the digge r-derrick truck, and the other two crewmembers were on the ground. The AWG 1/0 A SCR road-side and center phase conductors were 1.13 meters apart, and the four a rmor rods were about 1.3 meters long. The aerial lift bucket liner was 552 milli meters wide by 708 millimeters wide by 1.01 meters deep. As the employee was ins talling an armor rod on the road-side phase conductor, it apparently contacted a n uninsulated portion of the center phase conductor. This caused a phase-to-phas e electrical fault, which later enveloped the third phase. The employee received an electric shock and burns from the ensuing electric arc. He died with third-d egree burns over more than 60 percent of his body.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
OSH Act Section 5(a)(1) · General Duty Clause
Serious$7,000$5,000Dec 27, 2001Closed

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 2 reports on file.

Oct 6, 2022, Biloxi: Hospitalization · second degree electrical burns · arm(s), unspecified

A lineman was on a power pole holding a jumper wire. The wire contacted an energized primary line; the resulting arc flash caused first-degree burns to the lineman's face and second-degree burns to the lineman's right arm.

Apr 16, 2015, Columbus: Hospitalization · electrical burns, unspecified · face, unspecified

A utility line construction crew was in the process of replacing a wooden utility pole with a new metal utility pole and metal cross arm. After the new metal pole and cross arm was installed the crew wrapped an insulated blanket around the pole above the cross arm. Insulators were installed on the cross arm. A crew member was in a lift bucket and was using metal quick ties to connect the power…

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(l)(3)(iii)

(iii) The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless:

29 CFR 1926.960 · Working on or near exposed energized parts

29 CFR 1926.960(c)(1)(iii)

(iii) The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless:

29 CFR 1926.960(c)(2)(i)(a)

(A) Exposed energized parts on which the employee is not working are insulated from the employee; and

OSH Act Section 5 · General Duty Clause

Other power and communication line and related structures construction employers in Mississippi

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.