OSHA SearchOSHA records by employer

Northeast Texas Power, Ltd: OSHA inspections and violations

Joaquin, Texas · Power and Communication Line and Related Structures Construction · NAICS 237130

3inspections
3citation items
$8,660current penalties
Nov 10, 2020last inspection

Northeast Texas Power, Ltd has 3 OSHA inspections on record in Texas, the first in 2009.

OSHA's last visit started on Nov 10, 2020 after a fatality or catastrophe, in Mineola.

Across those inspections OSHA issued 3 citation items: 3 serious.

OSHA proposed $12,946 in penalties. After settlements and reviews the total is $8,660, down 33%.

Most often, OSHA cited 1926.952, job briefing (2 items).

For context, across all construction employers the median penalty per cited inspection since 2015 is $3,080. Northeast Texas Power, Ltd averages $5,160 over 1 cited inspection in that time.

2 inspections on this page followed a fatal incident.

It reported 1 severe injury to OSHA since 2015.

Northeast Texas Power, Ltd: OSHA citation items per year, 2009 to 2020
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

399employers cited

2 of them in the same industry

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Northeast Texas Power, Ltd and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 345030852 OPENED NOV 10, 2020Closed

Fatality or catastrophe · Partial · Safety · 6 employees at the site · Closed Apr 26, 2021

Fm 43, Mineola, TX 75773 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

Incident on Nov 6, 2020 (fatal): Employee is killed by electrocution while installing blanket

At 5:00 p.m. on November 6, 2020, an employee worked to install blankets for electrical wires. At some point, the employee made contact with an overhead transmission line and was killed by electrocution.

No citations from this inspection.

Inspection 344865381 OPENED AUG 3, 2020Closed

Referral · Complete · Safety · 5 employees at the site · Closed Dec 4, 2020

7936 Cr 294, Kilgore, TX 75662 · Electrical Apparatus and Equipment, Wiring Supplies, and Related Equipment Merchant Wholesalers · OSHA's record · Phone and website on Google Maps

Incident on Jul 30, 2020: Employee incurs burns by arc flash when installing jumper

At 3:00 p.m. on July 30, 2020, an employee was elevated in a bucket truck to install a jumper across a floater. The employee received an arc flash when he attempted to connect the power to a grounded circuit. The employee sustained 2nd degree burns to his face, chest and arm. The employee was hospitalized for treatment.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 2
29 CFR 1926.961(c)(13) · Deenergizing lines and equipment for employee protection
Serious$9,446$5,160Sep 3, 2020Final

Inspection 312119639 OPENED JAN 2, 2009Closed

Accident · Complete · Safety · 6 employees at the site · Closed Aug 25, 2010

Cr 3343, Joaquin, TX 75954 · Power and Communication Line and Related Structures Construction · OSHA's record · Phone and website on Google Maps

Incident on Dec 31, 2008 (fatal): Employee connecting power line is electrocuted

Employee #1, an electrical lineman, was working from an aerial lift bucket truck approximately 38 ft above the ground. Employee #1 was electrocuted when he was connecting a neutral line to a junction pole only thirty (30) inches beneath an exposed energized (7,200 volts) primary line. Employee #1 suffered an electric s hock and was electrocuted.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 4a
29 CFR 1926.952(a)(1) · Job briefing
Serious$3,500$3,500Jun 29, 2009Final
Citation 1, item 4b
29 CFR 1926.952(a)(2) · Job briefing
Serious$0$0Jun 29, 2009Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Nov 6, 2020, Mineola: Hospitalization · electrical burns, unspecified · multiple upper extremities locations, n.e.c.

An employee was in a bucket truck servicing the breakers and contacted an electrical line (7200V). The employee sustained burns and tissue damage to his left shoulder, arm and wrist.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.952 · Job briefing

29 CFR 1926.952(a)(1)

(a) Before each job—(1) Information provided by the employer. In assigning an employee or a group of employees to perform a job, the employer shall provide the employee in charge of the job with all available information that relates to the determination of existing characteristics and conditions required by § 1926.950(d).

29 CFR 1926.952(a)(2)

(2) Briefing by the employee in charge. The employer shall ensure that the employee in charge conducts a job briefing that meets paragraphs (b), (c), and (d) of this section with the employees involved before they start each job.

29 CFR 1926.961 · Deenergizing lines and equipment for employee protection

29 CFR 1926.961(c)(13)

(13) Reenergizing lines and equipment. The employer shall ensure that no one initiates action to reenergize the lines or equipment at a point of disconnection until all protective grounds have been removed, all crews working on the lines or equipment release their clearances, all employees are clear of the lines and equipment, and all protective tags are removed from that point of disconnection.

Other power and communication line and related structures construction employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.