OSHA SearchOSHA records by employer

Olon Ricerca Bioscience, LLC: OSHA inspections and violations

Painesville, Ohio · Research and Development in the Physical, Engineering, and Life Sciences · NAICS 541711

2inspections
9citation items
$39,935current penalties
Aug 25, 2021last inspection

OSHA has inspected Olon Ricerca Bioscience, LLC 2 times in Ohio since 2020.

The latest one began on Aug 25, 2021 on a referral, in Painesville.

Those inspections ended with 9 citation items: 8 serious and 1 other-than-serious.

Penalties were first proposed at $63,181 and now stand at $39,935, 37% lower after settlements or reviews.

Electrical equipment, general requirements comes up most often in these citations: 3 items under 1910.303.

How that compares: the median penalty per cited inspection for professional services employers since 2015 is $1,821, and Olon Ricerca Bioscience, LLC averages $19,968 (2 cited inspections).

It reported 1 severe injury to OSHA since 2015.

Olon Ricerca Bioscience, LLC: OSHA citation items per year, 2020 to 2021
Citation items per year, by inspection date.

Ohio · latest 90 days of OSHA records

273employers cited

Get notified the morning OSHA posts each new citation in Ohio: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Ohio

Checking a subcontractor, a client or your own company? Watch Olon Ricerca Bioscience, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 345497481 OPENED AUG 25, 2021Closed

Referral · Partial · Safety · 194 employees at the site · Closed Mar 7, 2022

7528 Auburn Road, Painesville, OH 44077 · Research and Development in the Physical, Engineering, and Life Sciences (except Nanotechnology and Biotechnology) · OSHA's record · Phone and website on Google Maps

Incident on Aug 22, 2021: Employee sustains burns in arc blast contacting conductor

At 1:30 p.m. on August 22, 2021, an employee working as an operations and maintenance technician for a bioscience research facility was troubleshooting an electrical system. The employee was investigating a power outage in Building B. The employee and a coworker, the facility supervisor, began troubleshooting the outage. The employee reset a switch in the outdoor substation, but the power did not return. The employee attempted to take a reading on one of the four lines that comes from the substation to an indoor 4160-Volt 6-Amp feeder. The feeder is located at Unit Substation 4 located in the penthouse of Building B. The employee opened a medium voltage transformer to access a switch located in the metal enclosed electrical cabinet to take a reading on the fuses when he caused an arc flash/blast. The employee was not wearing proper personal protective equipment, using proper electrical tools and had not received proper training in the high voltage electrical work. The employee was hospitalized to treat electrical shock and burns to his chest, arms, hands and fingers.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.147(c)(6)(i)(c) · Lockout/tagout
Serious$8,778$5,705Nov 15, 2021Final
Citation 1, item 2
29 CFR 1910.303(e)(1)(ii) · Electrical equipment, general requirements
Serious$8,778$5,705Nov 15, 2021Final
Citation 1, item 3a
29 CFR 1910.303(h)(5)(iii)(a) · Electrical equipment, general requirements
Serious$8,778$5,705Nov 15, 2021Final
Citation 1, item 3b
29 CFR 1910.303(h)(5)(iii)(b) · Electrical equipment, general requirements
Serious$0$0Nov 15, 2021Final
Citation 1, item 4 Serious$8,778$5,705Nov 15, 2021Final
Citation 1, item 5
29 CFR 1910.333(a)(2) · Working near live electrical parts
Serious$8,778$5,705Nov 15, 2021Final
Citation 1, item 6
29 CFR 1910.334(c)(3) · Using electrical equipment
Serious$8,778$5,705Nov 15, 2021Final
Citation 1, item 7
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$8,778$5,705Nov 15, 2021Final

Inspection 344701321 OPENED MAR 17, 2020Closed

Complaint · Partial · Health · 98 employees at the site · Closed May 20, 2021

7528 Auburn Road, Painesville, OH 44077 · Research and Development in the Physical, Engineering, and Life Sciences · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.1020(e)(1)(i) · Access to employee exposure and medical records
Other-than-serious$1,735$0May 8, 2020Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Aug 22, 2021, Painesville: Hospitalization · electrical burns, unspecified · multiple body parts, n.e.c.

While checking the source of an electrical failure, an employee suffered a high-voltage shock, with severe burns to the arms, legs, and torso.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.1020 · Access to employee exposure and medical records

29 CFR 1910.1020(e)(1)(i)

(e) Access to records—(1) General. (i) Whenever an employee or designated representative requests access to a record, the employer shall assure that access is provided in a reasonable time, place, and manner. If the employer cannot reasonably provide access to the record within fifteen (15) working days, the employer shall within the fifteen (15) working days apprise the employee or designated representative requesting the record of the reason for the delay and the earliest date when the record can be made available.

29 CFR 1910.147 · Lockout/tagout

29 CFR 1910.147(c)(6)(i)(c)

(C) Where lockout is used for energy control, the periodic inspection shall include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected.

29 CFR 1910.303 · Electrical equipment, general requirements

29 CFR 1910.303(e)(1)(ii)

(ii) Other markings giving voltage, current, wattage, or other ratings as necessary.

29 CFR 1910.332 · Training

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.334 · Using electrical equipment

29 CFR 1910.335 · Safeguards for personnel protection

Other research and development in the physical, engineering, and life sciences employers in Ohio

Alert subscribers get notified of each newly cited employer in Ohio the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.