OSHA SearchOSHA records by employer

Park Tower Apartments: OSHA inspections and violations

Lubbock, Texas · Lessors of Residential Buildings and Dwellings · NAICS 531110

2inspections
7citation items
$18,580current penalties
Jun 8, 2016last inspection

Since 2014, OSHA inspectors have visited Park Tower Apartments in Texas 2 times.

The most recent inspection opened on Jun 8, 2016 to follow up on an earlier case, in Lubbock.

In all, OSHA issued 7 citation items: 7 serious.

The proposed penalties came to $37,160; today they stand at $18,580, 50% less.

The rule cited most here is 1910.335 (safeguards for personnel protection), 2 times.

Among real estate and rental employers, the typical cited inspection since 2015 ends with a $1,857 penalty. Park Tower Apartments averages $3,080 across 1 cited inspection.

1 inspection on this page followed a fatal incident.

Park Tower Apartments: OSHA citation items per year, 2014 to 2016
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

401employers cited

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Park Tower Apartments and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 341538981 OPENED JUN 8, 2016Closed

Follow-up · Partial · Safety · 2 employees at the site · Closed Jan 2, 2018

1617 27th Street, Lubbock, TX 79411 · Lessors of Residential Buildings and Dwellings · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.147(c)(1) · Lockout/tagout
Serious$3,080$3,080Jul 8, 2016Final
Citation 1, item 1b
29 CFR 1910.147(c)(7)(i) · Lockout/tagout
Serious$3,080$0Jul 8, 2016Final

Inspection 339673089 OPENED APR 10, 2014Closed

Fatality or catastrophe · Partial · Safety · 6 employees at the site · Closed Jan 6, 2017

1617 27th Street, Suite 110, Lubbock, TX 79411 · Lessors of Residential Buildings and Dwellings · OSHA's record · Phone and website on Google Maps

Incident on Apr 10, 2014 (fatal): Employee sustains electrical burns and is killed

At 9:15 a.m. on April 10, 2014, an employee was advancing category five wire communication wire from a pool area to the ground floor at an apartment complex. Investigation and security video revealed that the employee entered a transformer closet with no warning signs, training, or personal protective equipment. Transformer electrical buses were in close proximity to the holes that were drilled in the floor and the ceiling to route the wiring. The employee came in contact with high voltage electricity. A witness stated the employee was found lying on the hall way floor with charred clothing and skin from the arc flash created by contact with the transformer. The employee died at the hospital.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.303(h)(5)(iii)(b) · Electrical equipment, general requirements
Serious$5,000$2,500Aug 14, 2014Final
Citation 1, item 2 Serious$7,000$3,500Aug 14, 2014Final
Citation 1, item 3
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$7,000$3,500Aug 14, 2014Final
Citation 1, item 4
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$7,000$3,500Aug 14, 2014Final
Citation 1, item 5
29 CFR 1910.335(a)(2)(i) · Safeguards for personnel protection
Serious$5,000$2,500Aug 14, 2014Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.147 · Lockout/tagout

29 CFR 1910.147(c)(1)

(c) General—(1) Energy control program. The employer shall establish a program consisting of energy control procedures, employee training and periodic inspections to ensure that before any employee performs any servicing or maintenance on a machine or equipment where the unexpected energizing, start up or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source, and rendered inoperative.

29 CFR 1910.147(c)(7)(i)

(7) Training and communication. (i) The employer shall provide training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of the energy controls are acquired by employees. The training shall include the following:

29 CFR 1910.303 · Electrical equipment, general requirements

29 CFR 1910.332 · Training

29 CFR 1910.332(b)(1)

(b) Content of training—(1) Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by §§ 1910.331 through 1910.335 that pertain to their respective job assignments.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.335 · Safeguards for personnel protection

Other lessors of residential buildings and dwellings employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.