OSHA SearchOSHA records by employer

Rural Solar Restoration, LLC: OSHA inspections and violations

Richmond, Texas · Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance · NAICS 811310

1inspections
3citation items
$9,268current penalties
Mar 18, 2025last inspection

Rural Solar Restoration, LLC has one OSHA inspection on record in Texas.

OSHA opened it on Mar 18, 2025 on a referral, in Richmond.

From that inspection OSHA issued 3 citation items: 2 serious and 1 other-than-serious.

OSHA proposed $26,481 in penalties. After settlements and reviews the total is $9,268, down 65%.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (3 items).

For context, across all repair and personal services employers the median penalty per cited inspection since 2015 is $1,200. Rural Solar Restoration, LLC averages $9,268 over 1 cited inspection in that time.

It reported 1 severe injury to OSHA since 2015.

Rural Solar Restoration, LLC: OSHA citation items per year, 2025 to 2025
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

399employers cited

5 of them in the same industry

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Rural Solar Restoration, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 348120171 OPENED MAR 18, 2025Closed

Referral · Partial · Safety · 2 employees at the site · Closed Sep 15, 2025

12907 Fm 361, Richmond, TX 77469 · Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(a)(2)(i)(a) · Electric power generation, transmission, and distribution
Other-than-serious$9,268$4,634Jul 17, 2025Final
Citation 1, item 2a
29 CFR 1910.269(d)(6)(vii) · Electric power generation, transmission, and distribution
Serious$9,268$4,634Jul 17, 2025Final
Citation 1, item 2b
29 CFR 1910.269(l)(8)(v) · Electric power generation, transmission, and distribution
Serious$7,945$0Jul 17, 2025Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Mar 15, 2025, Richmond: Hospitalization · electrical burns any degree · multiple body parts n.e.c.

An employee was repairing a solar panel inverter at a solar farm. The employee was working on a combiner box when an arc flash occurred. The employee sustained third-degree burns to their face, neck, and arm.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(2)(i)(a)

(A) Each employee shall be trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments.

29 CFR 1910.269(d)(6)(vii)

(vii) Before starting work on machines or equipment that have been locked out or tagged out, the authorized employee shall verify that isolation and deenergizing of the machine or equipment have been accomplished. If normally energized parts will be exposed to contact by an employee while the machine or equipment is deenergized, a test shall be performed to ensure that these parts are deenergized.

29 CFR 1910.269(l)(8)(v)

(v) The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm 2. This protective equipment shall cover the employee's entire body, except as follows:

Other commercial and industrial machinery and equipment (except automotive and electronic) repair and maintenance employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.