OSHA SearchOSHA records by employer

Stout Electric: OSHA inspections and violations

Las Vegas, Nevada · Electrical Contractors and Other Wiring Installation Contractors · NAICS 238210

2inspections
6citation items
$7,638current penalties
Dec 2, 2019last inspection

Since 2008, OSHA inspectors have visited Stout Electric in Nevada 2 times.

The most recent inspection opened on Dec 2, 2019 after an accident, in Henderson.

In all, OSHA issued 6 citation items: 5 serious and 1 other-than-serious.

The proposed penalties came to $14,615; today they stand at $7,638, 48% less.

The rule cited most here is 1910.335 (safeguards for personnel protection), 2 times.

Among construction employers, the typical cited inspection since 2015 ends with a $3,080 penalty. Stout Electric averages $7,300 across 1 cited inspection.

Stout Electric: OSHA citation items per year, 2008 to 2019
Citation items per year, by inspection date.

Nevada · latest 90 days of OSHA records

114employers cited

3 of them in the same industry

Get notified the morning OSHA posts each new citation in Nevada: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Nevada

Checking a subcontractor, a client or your own company? Watch Stout Electric and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344495783 OPENED DEC 2, 2019Closed

Accident · Partial · Safety · 17 employees at the site · Closed Dec 15, 2020

215 Codyerin Drive, Henderson, NV 89074 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Incident on Dec 2, 2019: Employee is shocked and incurs burns while removing live ele

At 9:30 a.m. on December 2, 2019, an employee was attempting to slide a bolt from behind the bus bar, to use for the new breaker. The employee was called to a mobile home park to replace a main breaker inside an energized 240-volt electrical panel. The employee arrived at the work site and began his task. The employee attempted to install a bolt for the new breaker with an un-insulated plier, which made contact with live conductors, causing an arc blast. The employee incurred electrical burns on the right side of the body from the right hand up to the neck area and face. Other factors included: incorrect PPE was used, employee was inexperienced, and lack of supervision. The employee sustained first to second degree burns to the right side of the forearm, up to the neck area and second to third degree burns on the right hand, up to the mid-forearm. The employee was hospitalized.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.333(a)(1) · Working near live electrical parts
Serious$3,470$3,470Sep 3, 2020Final
Citation 1, item 1b
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$3,470$0Sep 3, 2020Final
Citation 1, item 3a
29 CFR 1910.335(a)(2)(i) · Safeguards for personnel protection
Serious$3,470$3,470Sep 3, 2020Final
Citation 1, item 4b
29 CFR 1910.333(c)(2) · Working near live electrical parts
Serious$3,470$0Sep 3, 2020Final
Citation 2, item 1
29 CFR NEVADA REVISED STATUTES 618.383(1
Other-than-serious$360$360Sep 3, 2020Final

Inspection 312280647 OPENED OCT 21, 2008Closed

Referral · Partial · Safety · 12 employees at the site · Closed Feb 4, 2009

3890 Maryland Parkway, Las Vegas, NV 89119 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.67(c)(2)(v) · Vehicle-mounted elevating and rotating work platforms
Serious$375$338Dec 29, 2008Closed

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.333(a)(1)

(1) Deenergized parts. Live parts to which an employee may be exposed shall be deenergized before the employee works on or near them, unless the employer can demonstrate that deenergizing introduces additional or increased hazards or is infeasible due to equipment design or operational limitations. Live parts that operate at less than 50 volts to ground need not be deenergized if there will be no increased exposure to electrical burns or to explosion due to electric arcs.

29 CFR 1910.333(c)(2)

(2) Work on energized equipment. Only qualified persons may work on electric circuit parts or equipment that have not been deenergized under the procedures of paragraph (b) of this section. Such persons shall be capable of working safely on energized circuits and shall be familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools.

29 CFR 1910.335 · Safeguards for personnel protection

29 CFR 1910.335(a)(1)(i)

(a) Use of protective equipment—(1) Personal protective equipment. (i) Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.

29 CFR 1910.67 · Vehicle-mounted elevating and rotating work platforms

Other electrical contractors and other wiring installation contractors employers in Nevada

Alert subscribers get notified of each newly cited employer in Nevada the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.