OSHA SearchOSHA records by employer

Vicinity Energy, LLC: OSHA inspections and violations

Boston, Massachusetts · Steam and Air-Conditioning Supply · NAICS 221330

1inspections
3citation items
$14,500current penalties
Oct 15, 2021last inspection

Vicinity Energy, LLC has one OSHA inspection on record in Massachusetts.

OSHA opened it on Oct 15, 2021 on a referral, in Boston.

From that inspection OSHA issued 3 citation items: 3 other-than-serious.

OSHA proposed $14,502 in penalties. After settlements and reviews the total is $14,500, down 0%.

Most often, OSHA cited 1910.147, lockout/tagout (3 items).

For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Vicinity Energy, LLC averages $14,500 over 1 cited inspection in that time.

Vicinity Energy, LLC: OSHA citation items per year, 2021 to 2021
Citation items per year, by inspection date.

Massachusetts · latest 90 days of OSHA records

235employers cited

Get notified the morning OSHA posts each new citation in Massachusetts: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Massachusetts

Checking a subcontractor, a client or your own company? Watch Vicinity Energy, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 345581151 OPENED OCT 15, 2021Closed

Referral · Partial · Safety · 500 employees at the site · Closed Aug 1, 2022

165 Kneeland Street, Boston, MA 02111 · Steam and Air-Conditioning Supply · OSHA's record · Phone and website on Google Maps

Incident on Oct 15, 2021: Three employees incur burns and concussion from steam releas

At 9:30 a.m. on October 15, 2021, three employees were working near a steam boiler located at a hazardous waste collection facility. Employees #1 and #2 were employed with Clean Harbors Environmental, and Employee #3 worked for Vicinity Energy, LLC who owned the facility. The employees were working near an auxiliary steam system that feeds the boiler automizing steam to the burners and fuel oil heaters when a 6 in by 4 inch fitting failed on an auxiliary steam line operating at a nominal 200 psi. The cast iron tee fitting failure resulted in an explosion and release of high-pressure steam directly into the operating floor outside the control room. The steam release was accompanied by a loud high-pitched noise. Employees #1 and #2 received burned and scalding to the arms and back form the steam release, and Employee #3 suffered a concussion from the explosion. All three employees required hospitalization. Vicinity Energy, LLC did not have a steam trap maintenance program to ensure the proper operation of traps that drain off condensation to prevent damage to system parts and components.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 2a
29 CFR 1910.147(c)(2)(ii) · Lockout/tagout
Other-than-serious$14,502$14,500Mar 17, 2022Final
Citation 1, item 2b
29 CFR 1910.147(c)(4)(ii) · Lockout/tagout
Other-than-serious$0$0Mar 17, 2022Final
Citation 1, item 2c
29 CFR 1910.147(c)(6)(i) · Lockout/tagout
Other-than-serious$0$0Mar 17, 2022Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.147 · Lockout/tagout

29 CFR 1910.147(c)(2)(ii)

(ii) If an energy isolating device is capable of being locked out, the employer's energy control program under paragraph (c)(1) of this section shall utilize lockout, unless the employer can demonstrate that the utilization of a tagout system will provide full employee protection as set forth in paragraph (c)(3) of this section.

29 CFR 1910.147(c)(4)(ii)

(ii) The procedures shall clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, the following:

29 CFR 1910.147(c)(6)(i)

(6) Periodic inspection. (i) The employer shall conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed.

Other steam and air-conditioning supply employers in Massachusetts

Alert subscribers get notified of each newly cited employer in Massachusetts the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.