OSHA SearchOSHA records by employer

Cherokee County Electric Cooperative Association: OSHA inspections and violations

Whitehouse, Texas · Electric Bulk Power Transmission and Control · NAICS 221121

1inspections
1citation items
$7,168current penalties
Mar 16, 2021last inspection

OSHA has inspected Cherokee County Electric Cooperative Association once in Texas.

The inspection began on Mar 16, 2021 after a fatality or catastrophe, in Whitehouse.

That inspection ended with 1 citation item: 1 serious.

None of the citations carried a penalty.

How that compares: the median penalty per cited inspection for utility employers since 2015 is $0, and Cherokee County Electric Cooperative Association averages $7,168 (1 cited inspection).

1 inspection on this page followed a fatal incident.

Cherokee County Electric Cooperative Association: OSHA citation items per year, 2021 to 2021
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

399employers cited

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Cherokee County Electric Cooperative Association and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 345198261 OPENED MAR 16, 2021Closed

Fatality or catastrophe · Partial · Safety · 19 employees at the site · Closed Sep 28, 2021

20015 Cr 2147, Whitehouse, TX 75791 · Electric Bulk Power Transmission and Control · OSHA's record · Phone and website on Google Maps

Incident on Mar 15, 2021 (fatal): Employee dies after receiving electric shock

At 2:00 p.m. on March 15, 2021, Employee #1 and his coworkers were on site to install a utility pole and security light for a customer on personal property. The decision was made to perform the work without deenergizing the 14,400 volt power lines so that customers would not be affected. The crew had off loaded the pole into the ditch parallel to the utility lines however, the ground in the ditch was not firm enough so the foreman moved the vehicle up onto the roadway for more solid ground. The operator/foreman reset the outriggers on the digger derrick and was going to move the utility pole from the ditch, over the fence to the other side of the overhead power lines. When the lift was made, the mast of the derrick contacted one of the phases and the vehicle was energized. The operator was not injured; however, the employee who had rigged for the lift and was standing 3-5 feet away from the digger derrick, received an electrical shock. He was hospitalized and died from his injuries nine days later.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1b
29 CFR 1926.960(c)(1)(iii) · Working on or near exposed energized parts
Serious$0$7,168Aug 31, 2021Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.960 · Working on or near exposed energized parts

29 CFR 1926.960(c)(1)(iii)

(iii) The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance, unless: