OSHA SearchOSHA records by employer

East Mississippi Electric Power Association: OSHA inspections and violations

Ethel, Mississippi · Electric Power Distribution · NAICS 221122

3inspections
3citation items
$10,724current penalties
Aug 29, 2022last inspection

Since 2014, OSHA inspectors have visited East Mississippi Electric Power Association in Mississippi 3 times.

The most recent inspection opened on Aug 29, 2022 after a fatality or catastrophe, in Preston.

In all, OSHA issued 3 citation items: 3 serious.

The proposed penalties came to $13,674; today they stand at $10,724, 22% less.

The rule cited most here is 1910.269 (electric power generation, transmission, and distribution), 2 times.

Among utility employers, the typical cited inspection since 2015 ends with a $0 penalty. East Mississippi Electric Power Association averages $4,424 across 1 cited inspection.

2 inspections on this page followed a fatal incident.

It reported 1 severe injury to OSHA since 2015.

East Mississippi Electric Power Association: OSHA citation items per year, 2014 to 2022
Citation items per year, by inspection date.

Mississippi · latest 90 days of OSHA records

23employers cited

Get notified the morning OSHA posts each new citation in Mississippi: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Mississippi

Checking a subcontractor, a client or your own company? Watch East Mississippi Electric Power Association and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 346179161 OPENED AUG 29, 2022Closed

Fatality or catastrophe · Partial · Safety · 3 employees at the site · Closed Feb 28, 2023

Hwy 397 (approximately 2 1/2 Miles North Of Hwy 21), Preston, MS 39354 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Aug 29, 2022 (fatal): One employee is killed and two employees are injured when s

At 8:00 a.m. on August 29, 2022, an employee was working on a crew that was cutting down trees. The crew was performing line clearance for the East Mississippi Electric Power Association. The employee while standing off to the side within a clear/safe zone while a coworker was cutting down the tree. As the tree was falling, the coworker exited towards the clear/safe zone where the employee was standing. As the coworker entered the safe zone, a branch from an adjacent tree that was caught by the falling tree was ejected up and over the surrounding trees that protected the safe zone. The employee was killed when the branch struck him in the head. Two coworkers within the safe zone received minor injuries and were treated without hospitalization. All employees were wearing personal protective equipment (PPE) consisting of steel-toed boots, hard hats, safety glasses, gloves and saw chaps at the time of the incident.

No citations from this inspection.

Inspection 344521778 OPENED DEC 18, 2019Closed

Referral · Partial · Safety · 131 employees at the site · Closed Apr 14, 2020

Power Pole With Numbers 336 04 34 And 20 74 07 03 73, 1996 ,osmose 2010, Quitman, MS 39355 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Dec 17, 2019: Employee sustains flash burns after contacting power line

At 5:00 p.m. on December 17, 2019, an employee working as a lineman for a power distribution association was about to tighten a bolt on a lightning arrestor with his wrench. The employee made contact with the 7,200-Volt powerline and was shocked. The employee sustained a flash burn to his arm and was hospitalized.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1910.269(l)(1)(iii) · Electric power generation, transmission, and distribution
Serious$7,374$4,424Mar 16, 2020Final
Citation 1, item 1b
29 CFR 1910.269(n)(5) · Electric power generation, transmission, and distribution
Serious$0$0Mar 16, 2020Final

Inspection 339840225 OPENED JUL 9, 2014Closed

Fatality or catastrophe · Complete · Safety · 148 employees at the site · Closed Dec 17, 2014

9355 Attala Rd 5001, Ethel, MS 39067 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Jul 8, 2014 (fatal): Power line worker is electrocuted by contact with energized

At 2:45 p.m. on July 8, 2014, an employee was working for an electric power distribution utility. He was a member of a crew of power line workers. They were tapping into an existing overhead power line and routing a new power line to a meter pole located approximately 270 meters (880 feet) away. The employee was connecting overhead power lines to a transformer on a utility pole. A transformer had been installed on a dead-end pole next to the meter pole. As the employee was connecting the transformer to the new power line, the power line became energized, at 14.4 kV. Protective grounds had not been applied. The employee was electrocuted.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.954(f) · Personal protective equipment
Serious$6,300$6,300Nov 12, 2014Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Dec 17, 2019, Quitman: Hospitalization · electrical burns, unspecified · arm(s), unspecified

An employee was working on a distribution line after a storm, repairing a fused cutout switch that was 7,200 volts, when he contacted the live switch and received a flash burn on his right arm.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(l)(1)(iii)

(iii) Electric lines and equipment shall be considered and treated as energized unless they have been deenergized in accordance with paragraph (d) or (m) of this section.

29 CFR 1910.269(n)(5)

(5) Testing. The employer shall ensure that, unless a previously installed ground is present, employees test lines and equipment and verify the absence of nominal voltage before employees install any ground on those lines or that equipment.

29 CFR 1926.954 · Personal protective equipment

Other electric power distribution employers in Mississippi

Alert subscribers get notified of each newly cited employer in Mississippi the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.