OSHA SearchOSHA records by employer

Prentiss County Electric Power Association: OSHA inspections and violations

Baldwyn, Mississippi · Electric Power Distribution · NAICS 221122

1inspections
7citation items
$31,527current penalties
Apr 4, 2018last inspection

Prentiss County Electric Power Association has one OSHA inspection on record in Mississippi.

OSHA opened it on Apr 4, 2018 after a fatality or catastrophe, in Baldwyn.

From that inspection OSHA issued 7 citation items: 5 serious and 2 other-than-serious.

OSHA proposed $42,036 in penalties. After settlements and reviews the total is $31,527, down 25%.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (5 items).

For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Prentiss County Electric Power Association averages $31,527 over 1 cited inspection in that time.

1 inspection on this page followed a fatal incident.

Prentiss County Electric Power Association: OSHA citation items per year, 2018 to 2018
Citation items per year, by inspection date.

Mississippi · latest 90 days of OSHA records

23employers cited

Get notified the morning OSHA posts each new citation in Mississippi: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Mississippi

Checking a subcontractor, a client or your own company? Watch Prentiss County Electric Power Association and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 343060950 OPENED APR 4, 2018Closed

Fatality or catastrophe · Complete · Safety · 32 employees at the site · Closed Oct 29, 2018

586 Hwy 30 West, Baldwyn, MS 38824 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Apr 4, 2018 (fatal): Employee contact energized power line and is electrocuted

At 12:15 a.m. on April 4, 2018, Employee #1 responded to a power outage that occurred as a result of a tree falling on a power line. Employee #1 initially used a bucket truck to reach where the tree struck the line; however, the terrain was too muddy. He then used a safety harness to climb the utility pole, assuming the line was grounded. While ascending the utility pole, Employee #1 contacted the energized power line and was electrocuted. A nearby coworker, who heard a loud sound, looked back and saw Employee #1 hanging from the utility pole. The coworker immediately contacted emergency services.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.132(a) · Personal protective equipment, general requirements
Serious$6,596$4,947Oct 2, 2018Final
Citation 1, item 2
29 CFR 1910.269(c)(1)(ii) · Electric power generation, transmission, and distribution
Serious$9,054$6,790Oct 2, 2018Final
Citation 1, item 3
29 CFR 1910.269(g)(2)(i) · Electric power generation, transmission, and distribution
Serious$9,054$6,790Oct 2, 2018Final
Citation 1, item 4
29 CFR 1910.269(l)(8)(v) · Electric power generation, transmission, and distribution
Serious$4,398$3,298Oct 2, 2018Final
Citation 1, item 5
29 CFR 1910.269(n)(2) · Electric power generation, transmission, and distribution
Serious$12,934$9,700Oct 2, 2018Final
Citation 2, item 1
29 CFR 1910.137(c)(2)(viii) · Electrical protective equipment
Other-than-serious$0$0Oct 2, 2018Final
Citation 2, item 2
29 CFR 1910.269(j)(2)(iii) · Electric power generation, transmission, and distribution
Other-than-serious$0$0Oct 2, 2018Final

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.132 · Personal protective equipment, general requirements

29 CFR 1910.132(a)

(a) Application. Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, shall be provided, used, and maintained in a sanitary and reliable condition wherever it is necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation or physical contact.

29 CFR 1910.137 · Electrical protective equipment

29 CFR 1910.137(c)(2)(viii)

(viii) Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-4 and Table I-5.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(c)(1)(ii)

(ii) The employer shall ensure that the employee in charge conducts a job briefing that meets paragraphs (c)(2), (c)(3), and (c)(4) of this section with the employees involved before they start each job.

Other electric power distribution employers in Mississippi

Alert subscribers get notified of each newly cited employer in Mississippi the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.