Entergy Mississippi, LLC has 4 OSHA inspections on record in Mississippi, the first in 2001.
OSHA's last visit started on Aug 25, 2020 on a referral, in French Camp.
Across those inspections OSHA issued 7 citation items: 7 serious.
OSHA proposed $49,684 in penalties. After settlements and reviews the total is $28,550, down 43%.
Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (3 items).
For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Entergy Mississippi, LLC averages $11,125 over 2 cited inspections in that time.
Entergy Mississippi, LLC also files yearly injury logs with OSHA, summarized below.
It reported 1 severe injury to OSHA since 2015.
Citation items per year, by inspection date.
Mississippi · latest 90 days of OSHA records
18employers cited
Get notified the morning OSHA posts each new citation in Mississippi: the employer, the site address, the rules broken and the penalty.
Incident on Aug 20, 2020: Employee lacerates thumb when struck by rotating fan blade
At 1:45 p.m. on August 20, 2020, an employee was inspecting brushes on a generator. The employee's left thumb was struck by and cut by the rotating fan. The employee was treated without hospitalization.
Incident on Nov 14, 2019: Employees working on transformer are burned by arc flash
At 8:00 a.m. on November 14, 2019, three employees were working for an integrated electric power utility. It produced and distributed electricity. The employees installed and repaired electric power equipment. The employees had been working for twenty-four hours. They were fifteen minutes into the twenty-fifth hour when the incident occurred. The three employees were phasing (verifying the voltage of) a run of 480-volt cables and a transformer that they had installed in a below ground electrical vault to replace existing equipment. The leads for the multimeter were too short to reach the contact points of the three phase conductors that were to be tested. The employees improvised by utilizing a spare cable to bridge the gap. The lead journeyman cable splicer and Employee #1 held the cable. The lead employee was to make contact with each energized phase with his end of the cable while Employee #1 was to hold his end of the cable in open air for Employee #2 to touch the exposed end with a probe from the multimeter. The lead employee gave the command that he was energizing the cable, and the command was confirmed by Employees #1 and #2. When the multimeter lead made contact with the energized cable, Employee #1 inadvertently made contact with the transformer's protector. An arc flash ensued. The two employees were not wearing arc-rated protective clothing, and Employee #1 was not wearing a face shield. Employee #1 was hospitalized to treat second- and third-degree burns. Employee #2 was hospitalized to treat first degree burns.
From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.
In 2025, the Jackson site logged 0 recordable injuries or illnesses among about 68 workers: 0.0 per 100 full-time workers, against a median of 1.0 for its industry.
Site and year
Workers
Cases
Days-away cases
Rate
Industry median
Jackson Network
Jackson · 2025
68
0
0
0.0
1.0
South St. Office
Jackson · 2025
73
0
0
0.0
1.0
EMI Headquarters (Electric Buliding)
Jackson · 2025
54
0
0
0.0
1.0
Madison Network
Madison · 2025
45
0
0
0.0
1.0
Hinds Energy Facility
Jackson · 2025
37
0
0
0.0
1.0
Mayes St. Office
Jackson · 2025
17
0
0
0.0
1.0
Supply Chain Operations Mississippi Distribution Center
Jackson · 2020
7
0
0
0.0
1.0
Lakeover Substation
Jackson · 2019
5
0
0
0.0
1.0
Included with any plan: 42 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.
(a) Machine guarding—(1) Types of guarding. One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are—barrier guards, two-hand tripping devices, electronic safety devices, etc.
(11) Portable ladders used to gain access to an upper landing surface have side rails that extend at least 3 feet (0.9 m) above the upper landing surface (see Figure D-1 of this section);
29 CFR 1910.269 · Electric power generation, transmission, and distribution
29 CFR 1910.269(a)(2)(i)(b)
(B) Each employee shall also be trained in and familiar with any other safety practices, including applicable emergency procedures (such as pole-top and manhole rescue), that are not specifically addressed by this section but that are related to his or her work and are necessary for his or her safety.
29 CFR 1926.950 · Electric Power Transmission and Distribution: general
Alert subscribers get notified of each newly cited employer in Mississippi the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.