OSHA SearchOSHA records by employer

Entergy Mississippi, LLC: OSHA inspections and violations

Madison, Mississippi · Electric Power Distribution · NAICS 221122

4inspections
7citation items
$28,550current penalties
Aug 25, 2020last inspection

Entergy Mississippi, LLC has 4 OSHA inspections on record in Mississippi, the first in 2001.

OSHA's last visit started on Aug 25, 2020 on a referral, in French Camp.

Across those inspections OSHA issued 7 citation items: 7 serious.

OSHA proposed $49,684 in penalties. After settlements and reviews the total is $28,550, down 43%.

Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (3 items).

For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Entergy Mississippi, LLC averages $11,125 over 2 cited inspections in that time.

Entergy Mississippi, LLC also files yearly injury logs with OSHA, summarized below.

It reported 1 severe injury to OSHA since 2015.

Entergy Mississippi, LLC: OSHA citation items per year, 2001 to 2020
Citation items per year, by inspection date.

Mississippi · latest 90 days of OSHA records

18employers cited

Get notified the morning OSHA posts each new citation in Mississippi: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Mississippi

Checking a subcontractor, a client or your own company? Watch Entergy Mississippi, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 344897749 OPENED AUG 25, 2020Closed

Referral · Partial · Safety · 28 employees at the site · Closed Mar 24, 2021

2446 Ms Hwy 407, French Camp, MS 39745 · Fossil Fuel Electric Power Generation · OSHA's record · Phone and website on Google Maps

Incident on Aug 20, 2020: Employee lacerates thumb when struck by rotating fan blade

At 1:45 p.m. on August 20, 2020, an employee was inspecting brushes on a generator. The employee's left thumb was struck by and cut by the rotating fan. The employee was treated without hospitalization.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.212(a)(1) · Machine guarding
Serious$13,653$8,192Jan 25, 2021Final

Inspection 344450721 OPENED NOV 15, 2019Closed

Referral · Partial · Safety · 4 employees at the site · Closed Mar 13, 2020

100 West Capitol Street, Jackson, MS 39269 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Nov 14, 2019: Employees working on transformer are burned by arc flash

At 8:00 a.m. on November 14, 2019, three employees were working for an integrated electric power utility. It produced and distributed electricity. The employees installed and repaired electric power equipment. The employees had been working for twenty-four hours. They were fifteen minutes into the twenty-fifth hour when the incident occurred. The three employees were phasing (verifying the voltage of) a run of 480-volt cables and a transformer that they had installed in a below ground electrical vault to replace existing equipment. The leads for the multimeter were too short to reach the contact points of the three phase conductors that were to be tested. The employees improvised by utilizing a spare cable to bridge the gap. The lead journeyman cable splicer and Employee #1 held the cable. The lead employee was to make contact with each energized phase with his end of the cable while Employee #1 was to hold his end of the cable in open air for Employee #2 to touch the exposed end with a probe from the multimeter. The lead employee gave the command that he was energizing the cable, and the command was confirmed by Employees #1 and #2. When the multimeter lead made contact with the energized cable, Employee #1 inadvertently made contact with the transformer's protector. An arc flash ensued. The two employees were not wearing arc-rated protective clothing, and Employee #1 was not wearing a face shield. Employee #1 was hospitalized to treat second- and third-degree burns. Employee #2 was hospitalized to treat first degree burns.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.23(c)(11) · Ladders in general industry
Serious$5,407$3,244Feb 10, 2020Final
Citation 1, item 2
29 CFR 1910.269(a)(2)(i)(b) · Electric power generation, transmission, and distribution
Serious$9,012$5,407Feb 10, 2020Final
Citation 1, item 3a
29 CFR 1910.269(l)(8)(v) · Electric power generation, transmission, and distribution
Serious$9,012$5,407Feb 10, 2020Final
Citation 1, item 3b
29 CFR 1910.269(l)(8)(v)(d) · Electric power generation, transmission, and distribution
Serious$0$0Feb 10, 2020Final

Inspection 339978538 OPENED SEP 25, 2014Closed

Referral · Complete · Safety · 12 employees at the site · Closed Nov 18, 2014

Corner Of White Blvd And Old Hwy 24, Mccomb, MS 39648 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 304311475 OPENED OCT 25, 2001Closed

Unprogrammed related · Partial · Safety · 4 employees at the site · Closed Jun 5, 2002

Hwy 51 Church, Madison, MS 39110 · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.950(d)(1) · Electric Power Transmission and Distribution: general
Serious$6,300$6,300Mar 25, 2002Closed
Citation 1, item 2
29 CFR 1926.954(f) · Personal protective equipment
Serious$6,300$0Mar 25, 2002Closed

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2025, the Jackson site logged 0 recordable injuries or illnesses among about 68 workers: 0.0 per 100 full-time workers, against a median of 1.0 for its industry.

Site and yearWorkersCasesDays-away casesRateIndustry median
Jackson Network
Jackson · 2025
68 000.01.0
South St. Office
Jackson · 2025
73 000.01.0
EMI Headquarters (Electric Buliding)
Jackson · 2025
54 000.01.0
Madison Network
Madison · 2025
45 000.01.0
Hinds Energy Facility
Jackson · 2025
37 000.01.0
Mayes St. Office
Jackson · 2025
17 000.01.0
Supply Chain Operations Mississippi Distribution Center
Jackson · 2020
7 000.01.0
Lakeover Substation
Jackson · 2019
5 000.01.0

Included with any plan: 42 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.

See plans

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Nov 13, 2019, Jackson: Hospitalization · electrical burns, unspecified · face, unspecified

Two employees were phasing out a new run of cable when an arc flash occurred, causing burns to their faces that required hospitalization.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.212 · Machine guarding

29 CFR 1910.212(a)(1)

(a) Machine guarding—(1) Types of guarding. One or more methods of machine guarding shall be provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks. Examples of guarding methods are—barrier guards, two-hand tripping devices, electronic safety devices, etc.

29 CFR 1910.23 · Ladders in general industry

29 CFR 1910.23(c)(11)

(11) Portable ladders used to gain access to an upper landing surface have side rails that extend at least 3 feet (0.9 m) above the upper landing surface (see Figure D-1 of this section);

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(2)(i)(b)

(B) Each employee shall also be trained in and familiar with any other safety practices, including applicable emergency procedures (such as pole-top and manhole rescue), that are not specifically addressed by this section but that are related to his or her work and are necessary for his or her safety.

29 CFR 1926.950 · Electric Power Transmission and Distribution: general

29 CFR 1926.954 · Personal protective equipment

Other electric power distribution employers in Mississippi

Alert subscribers get notified of each newly cited employer in Mississippi the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.