OSHA SearchOSHA records by employer

Ferrie Franzmann Industries, LLC: OSHA inspections and violations

Dallas, Texas · Electric Power Distribution · NAICS 221122

1inspections
9citation items
$51,610current penalties
Jul 2, 2021last inspection

OSHA inspectors have visited Ferrie Franzmann Industries, LLC in Texas one time.

It opened on Jul 2, 2021 on a referral, in Dallas.

In all, OSHA issued 9 citation items: 9 serious.

The proposed penalties came to $110,592; today they stand at $51,610, 53% less.

The rule cited most here is 1910.269 (electric power generation, transmission, and distribution), 6 times.

Among utility employers, the typical cited inspection since 2015 ends with a $0 penalty. Ferrie Franzmann Industries, LLC averages $51,610 across 1 cited inspection.

It reported 1 severe injury to OSHA since 2015.

Ferrie Franzmann Industries, LLC: OSHA citation items per year, 2021 to 2021
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

399employers cited

4 of them in the same industry

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Ferrie Franzmann Industries, LLC and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 345399315 OPENED JUL 2, 2021Closed

Referral · Partial · Safety · 2 employees at the site · Closed Dec 1, 2021

1020 Sargent Rd, Dallas, TX 75235 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Jun 29, 2021: Two employees sustain burns in arc flash testing switchgear

At 8:00 a.m. on June 29, 2021, Employee #1 and Employee #2, both working as electricians for an electrical power distributor, were preparing to install switchgear. The crew was testing for electrical power in the switchgear. One employee bypassed the shutters within the back of the electrical box in order to access the electrical contacts. The employee then used a digital multimeter to attempt to check for power. When the employee put the leads on the energized contacts an arc event occurred. Both employees were hospitalized to treat electrical burns to multiple parts of their bodies.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(a)(2)(ii)(e) · Electric power generation, transmission, and distribution
Serious$12,288$7,373Oct 26, 2021Final
Citation 1, item 2
29 CFR 1910.269(a)(3)(iii) · Electric power generation, transmission, and distribution
Serious$12,288$0Oct 26, 2021Final
Citation 1, item 3
29 CFR 1910.269(l)(1)(iii) · Electric power generation, transmission, and distribution
Serious$12,288$7,373Oct 26, 2021Final
Citation 1, item 4
29 CFR 1910.269(m)(2)(i) · Electric power generation, transmission, and distribution
Serious$12,288$7,373Oct 26, 2021Final
Citation 1, item 5
29 CFR 1910.269(m)(3)(ii) · Electric power generation, transmission, and distribution
Serious$12,288$0Oct 26, 2021Final
Citation 1, item 6
29 CFR 1910.269(u)(4)(iii) · Electric power generation, transmission, and distribution
Serious$12,288$7,373Oct 26, 2021Final
Citation 1, item 7
29 CFR 1910.333(c)(2) · Working near live electrical parts
Serious$12,288$7,373Oct 26, 2021Final
Citation 1, item 8
29 CFR 1910.334(c)(3) · Using electrical equipment
Serious$12,288$7,373Oct 26, 2021Final
Citation 1, item 9
29 CFR 1910.335(a)(1)(i) · Safeguards for personnel protection
Serious$12,288$7,373Oct 26, 2021Final

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Jun 29, 2021, Dallas: Hospitalization · electrical burns, unspecified · nonclassifiable

Two employees were preparing to install new circuit breakers in medium-voltage switchgear. While testing for electrical power in the switchgear, an arc flash occurred. Both employees sustained electrical burns.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(2)(ii)(e)

(E) The recognition of electrical hazards to which the employee may be exposed and the skills and techniques necessary to control or avoid these hazards.

29 CFR 1910.269(a)(3)(iii)

(iii) The contract employer and the host employer shall coordinate their work rules and procedures so that each employee of the contract employer and the host employer is protected as required by this section.

29 CFR 1910.269(l)(1)(iii)

(iii) Electric lines and equipment shall be considered and treated as energized unless they have been deenergized in accordance with paragraph (d) or (m) of this section.

29 CFR 1910.333 · Working near live electrical parts

29 CFR 1910.334 · Using electrical equipment

29 CFR 1910.335 · Safeguards for personnel protection

Other electric power distribution employers in Texas

Alert subscribers get notified of each newly cited employer in Texas the morning it is posted. See the alert plans.