Jersey Central Power & Light Company has 41 OSHA inspections on record in New Jersey, the first in 1976.
OSHA's last visit started on Apr 6, 2026 on a referral, in Lebanon, and the case has not closed yet.
Across those inspections OSHA issued 61 citation items: 15 serious and 46 other-than-serious.
OSHA proposed $119,631 in penalties. After settlements and reviews the total is $116,140, down 3%.
Most often, OSHA cited 1910.269, electric power generation, transmission, and distribution (8 items).
For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Jersey Central Power & Light Company averages $21,883 over 3 cited inspections in that time.
7 inspections on this page followed a fatal incident.
Jersey Central Power & Light Company also files yearly injury logs with OSHA, summarized below.
It reported 1 severe injury to OSHA since 2015.
Citation items per year, by inspection date.
New Jersey · latest 90 days of OSHA records
270employers cited
Get notified the morning OSHA posts each new citation in New Jersey: the employer, the site address, the rules broken and the penalty.
Checking a subcontractor, a client or your own company? Watch Jersey Central Power & Light Company and get notified the morning OSHA posts a new citation for it.
Incident on May 17, 2017 (fatal): Employee contacts live electrical parts and is killed
At 11:00 a.m. on May 17, 2017, an employee was opening a ground mounted 7.2 kv electrical transformer box.The employee slipped and contacted live parts with his hand. The employee was shocked and killed by the live electrical parts.
No citations from this inspection.
Inspection 341474393 OPENED MAY 13, 2016Closed
Referral · Complete · Safety · 200 employees at the site · Closed Sep 13, 2016
Incident on Aug 3, 2012 (fatal): Electric shock - direct contact with an energized conductor
At 10:00 a.m. on August 3, 2012, an employee was working as a line worker for the electric utility Jersey Central Power & Light Company. He had just gotten his work gloves, and he was walking back to a location where work was going to be performed. He was walking along a path in a swampy area, when he slipped. He made contact with an overhead power line conductor that had fallen and was on the ground. It was energized, and he was electrocuted.
Incident on Aug 10, 2009 (fatal): Employee is burned by electrical shock, later dies
On August 10, 2009, a crew of seven employees was performing routine maintenance on breaker T98 of a substation. The T98 breaker had been tagged out, switched, and grounded on both sides. Employee #1 received an electrical shock when he acc essed breaker S19, which had not been tagged out, switched, or grounded. He sust ained second and third degree burns to over 80 percent of his body. Employee #1 was transported to a burn unit. A coma was induced, and he remained in that stat e until his death on August 16, 2009.
Incident on Dec 6, 2004 (fatal): Electric shock - possible contact with overhead line
A power line worker was working from the bucket of an articulating-boom aerial l ift, connecting a 120/240-volt service line to an overhead secondary line above him. A coworker on the ground noticed that the power line worker was unresponsiv e, and he lowered the bucket to the ground. Emergency medical services transport ed the injured employee to a hospital, where he was pronounced dead. (The origin al form stated that the employee suffered a cardiac arrest, but did not indicate whether it was caused by an electric shock.)
No citations from this inspection.
Inspection 307614396 OPENED APR 26, 2004Closed
Complaint · Partial · Health · 51 employees at the site · Closed Sep 22, 2004
Incident on Mar 6, 1993 (fatal): Electric shock - direct contact with overhead line
A TWO-PERSON ELECTRIC UTILITY CREW WAS ASSIGNED TO REPAIR AN OVERHEAD POWER LINE . THE CENTER PHASE CONDUCTOR OF THE 7200-VOLT, THREE-PHASE OVERHEAD LINE WAS OPE N, AND ONE END OF THIS CONDUCTOR WAS HANGING DOWN OVER A TREE ABOUT 6 FEET FROM THE GROUND. THE OTHER END OF THE CONDUCTOR WAS STILL IN A TREE. THE CREW CHIEF O PENED THE SUPPLY SIDE OF THE CENTER PHASE AND ONE OUTSIDE PHASE CONDUCTOR BY OPE NING THE CORRESPONDING FUSED CUTOUTS. THE OTHER PHASE CONDUCTOR WAS LEFT ENERGIZ ED SINCE IT FED TWO BUILDINGS AND DID NOT EXTEND TO THE POLE WHERE THE BREAK WAS . THE CREW CHIEF TOLD THE OTHER POWER LINE WORKER TO DON HIS PERSONAL PROTECTIVE EQUIPMENT AND TO GO UP IN AN AERIAL LIFT TO REPAIR THE CONDUCTOR. THE CREW CHIE F THEN GOT SPLICING TOOLS AND A COIL OF WIRE AND WENT TO THE CONDUCTOR THAT WAS HANGING DOWN FROM THE TREE. WITHOUT USING ELECTRICAL PROTECTIVE EQUIPMENT, HE CO NTACTED THE DOWNED CONDUCTOR WITH HIS RIGHT HAND AND WAS ELECTROCUTED. THE CONDU CTOR WAS ENERGIZED BY VOLTAGE BACKFEED FROM TRANSFORMERS IN THE BUILDINGS.
Incident on Aug 6, 1992 (fatal): Electric shock - direct contact with energized parts
A POWER LINE WORKER WAS WORKING ON A PAD-MOUNTED TRANSFORMER USED WITH AN UNDERG ROUND RESIDENTIAL DISTRIBUTION SYSTEM. HE WAS NOT USING ELECTRICAL PROTECTIVE EQ UIPMENT. HE CONTACTED ONE OF THE 120-VOLT SECONDARY CONDUCTORS AND THE GROUNDED CASE OF THE TRANSFORMER. HE WAS ELECTROCUTED.
No citations from this inspection.
Inspection 17852518 OPENED SEP 6, 1991Closed
Accident · Partial · Safety · 45 employees at the site · Closed Jan 24, 1992
Incident on Sep 6, 1991 (fatal): Electric shock - direct contact with energized parts
AN ELECTRIC UTILITY EMPLOYEE WAS INSTALLING ABOVE-GROUND TO UNDERGROUND WIRING. HE WAS NOT USING RUBBER INSULATING EQUIPMENT WHILE HE WAS WORKING WITH ENERGIZED PARTS OF THE 7200-VOLT ELECTRIC CIRCUIT. THE EMPLOYEE WAS ELECTROCUTED.
From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.
In 2022, the Morristown site logged 11 recordable injuries or illnesses among about 1,091 workers: 1.0 per 100 full-time workers, against a median of 1.0 for its industry. Those cases cost 247 days away from work.
Site and year
Workers
Cases
Days-away cases
Rate
Industry median
Jersey Central Power & Light
Morristown · 2022
1,091
11
8
1.0
1.0
Severe injury reports
Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.
Sep 30, 2024, East Hanover: Hospitalization · electrical burns any degree · abdomen unspecified
A line crew was in the process of transferring a three-phase primary spacer cable when the energized cable unexpectedly detached from the bracket and contacted an employee in the chest area. The injured employee was hospitalized for abdominal burns.
The rules behind these citations
Current text from the Code of Federal Regulations. Some citations were issued under older wording.
29 CFR 1904.2 · Partial exemption for establishments in certain industries
(b) Implementation—(1) What do I need to do to complete the OSHA 300 Log? You must enter information about your business at the top of the OSHA 300 Log, enter a one or two line description for each recordable injury or illness, and summarize this information on the OSHA 300-A at the end of the year.
(3) How do I record a work-related injury or illness that results in days away from work? When an injury or illness involves one or more days away from work, you must record the injury or illness on the OSHA 300 Log with a check mark in the space for cases involving days away and an entry of the number of calendar days away from work in the number of days column. If the employee is out for an extended period of time, you must enter an estimate of the days that the employee will be away, and update the day count when the actual number of days is known.
Alert subscribers get notified of each newly cited employer in New Jersey the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.