17inspections
7citation items
$30,060current penalties
Apr 2, 2019last inspection

Kansas City Power and Light Co. has 17 OSHA inspections on record in Kansas, the first in 1977.

OSHA's last visit started on Apr 2, 2019 on a referral, in Spearville.

Across those inspections OSHA issued 7 citation items: 4 serious and 3 other-than-serious.

OSHA proposed $34,260 in penalties. After settlements and reviews the total is $30,060, down 12%.

Most often, OSHA cited 1926.950, electric power transmission and distribution: general (3 items).

For context, across all utility employers the median penalty per cited inspection since 2015 is $0. Kansas City Power and Light Co. averages $13,260 over 1 cited inspection in that time.

5 inspections on this page followed a fatal incident.

Kansas City Power and Light Co. also files yearly injury logs with OSHA, summarized below.

It reported 1 severe injury to OSHA since 2015.

Kansas City Power and Light Co.: OSHA citation items per year, 1977 to 2019
Citation items per year, by inspection date.

Kansas · latest 90 days of OSHA records

48employers cited

Get notified the morning OSHA posts each new citation in Kansas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Kansas

Checking a subcontractor, a client or your own company? Watch Kansas City Power and Light Co. and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 343898904 OPENED APR 2, 2019Closed

Referral · Complete · Safety · 7 employees at the site · Closed Dec 17, 2019

10311 126th Rd., Spearville, KS 67876 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Mar 22, 2019: Employee is struck by falling tools and is injured

At 3:00 p.m. on March 22, 2019, an employee was standing near the door entrance and a tool became detached, striking the employee. The tool struck the worker on side of the head, and he sustained an unspecified head injured. The employee was hospitalized for this injury.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
OSH Act Section 5(a)(1) · General Duty Clause
Serious$13,260$13,260May 21, 2019Final

Inspection 314028671 OPENED JUL 28, 2010Closed

Planned · Complete · Safety · 20 employees at the site · Closed Jul 28, 2010

5200 Roe Blvd, Mission, KS 66202 · Electrical Contractors and Other Wiring Installation Contractors · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 306169939 OPENED JUL 31, 2003Closed

Planned · No inspection · Safety · Closed Jul 31, 2003

Old Kc And Lone Star Rd, Osawatomie, KS 66064 · Fossil Fuel Electric Power Generation · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 305024333 OPENED FEB 1, 2002Closed

Accident · Complete · Safety · 200 employees at the site · Closed Jun 21, 2002

87th & State Line, Leawood, KS 66201 · OSHA's record · Phone and website on Google Maps

Incident on Jan 16, 2002 (fatal): Electric shock - direct contact with energized parts

A power line worker was working from the bucket of an aerial lift about 17 meter s above the ground. He contacted a fused disconnect on a utility pole and was el ectrocuted.

No citations from this inspection.

Inspection 303799043 OPENED JUN 7, 2001Closed

Referral · Partial · Safety · 200 employees at the site · Closed Nov 6, 2001

107th Sw Lackman Rd, Lenexa, KS 66215 · OSHA's record · Phone and website on Google Maps

Incident on Jun 7, 2001: Burn - electrical fault in overhead power line

An employee on a power line crew was replacing a 600-ampere switch on one phase of a 7200-volt overhead power line. He was working from a two-bucket aerial lift and was in the bucket closest to the switch. The jumper contacted the grounded switch bracket and caused an electrical fault. The ensuing electric arc burned t he employee. He was hospitalized with second- and third-degree burns to 50 perce nt of his body.

No citations from this inspection.

Inspection 303798888 OPENED MAY 30, 2001Closed

Accident · Partial · Safety · 200 employees at the site · Closed Nov 6, 2001

159th & Mur-lyn Rd, Olathe, KS 66062 · OSHA's record · Phone and website on Google Maps

Incident on May 29, 2001 (fatal): Electric shock & fall - direct contact with overhead line

A power line crew was in the final phases of construction of a new double-circui t overhead power line. The lower circuit was energized to the west side of the s econd utility pole supporting the new power line. An apprentice line worker clim bed the pole to remove protective grounds on the east side of the pole. He conta cted the energized side of the 7200-volt (phase-to-ground) power line, received an electric shock, and was knocked from the pole. He fell 9.8 meters to the grou nd. He died of his injuries.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1a
29 CFR 1926.950(b)(1) · Electric Power Transmission and Distribution: general
Serious$7,000$5,600Oct 1, 2001Closed
Citation 1, item 2
29 CFR 1926.950(b)(2) · Electric Power Transmission and Distribution: general
Serious$7,000$5,600Oct 1, 2001Closed
Citation 1, item 3
29 CFR 1926.950(c)(1) · Electric Power Transmission and Distribution: general
Serious$7,000$5,600Oct 1, 2001Closed

Inspection 106020894 OPENED JAN 9, 1990Closed

Accident · Partial · Safety · 159 employees at the site · Closed Jan 18, 1990

159th & Mur-lyn Rd, Olathe, KS 66062 · OSHA's record · Phone and website on Google Maps

Incident on Dec 19, 1989 (fatal): Fall - failure of utility pole

A CREW OF POWER LINE WORKERS FOR AN ELECTRIC UTILITY WAS REMOVING CONDUCTORS FRO M A UTILITY POLE. ONE OF THE CONDUCTORS SLIPPED FROM A GRIP THEY WERE USING AND FELL TO THE GROUND. IT BECAME STUCK BETWEEN THE BED AND THE CAB OF A GLASS HAULI NG TRUCK THAT HAD BEEN MOVING DOWN THE STREET. THE TRUCK PULLED THE CONDUCTOR, C AUSING THE TOP 19 FEET OF THE POLE TO SNAP OFF. ONE OF THE EMPLOYEES WAS BELTED TO THE POLE AND FELL WITH IT, LANDING ON HIS UPPER TORSO. HE WAS TAKEN TO A HOSP ITAL WHERE HE DIED 18 DAYS LATER.

Incident on Dec 19, 1989 (fatal): Fall - utility pole broke

A power line crew was removing conductors from a utility pole. One of the conduc tors slipped loose from a grip the employees were using and fell to the ground. It became stuck between the cab and the bed of a glass hauling truck that was tr aveling down the street. The truck pulled the conductor with it, causing the top 5.8 meters (19 feet) of the pole to break off. One of the power line workers wa s belted to the pole and fell with it to the ground. He landed on his upper tors o. He was transported to a hospital, where he died of his injuries nearly 9 mont hs after the accident, on August 6, 1990 at about 8:30 PM.

No citations from this inspection.

Inspection 18269894 OPENED MAR 11, 1987Closed

Complaint · Partial · Health · 330 employees at the site · Closed Mar 11, 1987

La Cygne Power Station, Rt. #1, La Cygne, KS 66040 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

9 older inspections

Inspection 18272302 OPENED DEC 16, 1986Closed

Complaint · Partial · Safety · 300 employees at the site · Closed Dec 23, 1986

West Hwy. 56 - Moonlight Rd., Moonlight Substation, Gardner, KS 66030 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 2473049 OPENED NOV 26, 1985Closed

Accident · Partial · Safety · 270 employees at the site · Closed Oct 30, 1986

Ne Corner Of 107th & Roe, Overland Park, KS 66211 · OSHA's record · Phone and website on Google Maps

Incident on Nov 21, 1985 (fatal): Electric shock - direct contact with energized part

AN EMPLOYEE WAS CONNECTING A SINGLE-PHASE CABLE TO THE DEENERGIZED SIDE OF THE S WITCH FOR ONE PHASE OF A THREE-PHASE SYSTEM. HIS RIGHT HAND APPARENTLY CONTACTED THE SWITCH FOR ANOTHER ENERGIZED PHASE IN THE ADJACENT COMPARTMENT.

No citations from this inspection.

Inspection 217497148 OPENED OCT 3, 1983Closed

Planned · Partial · Health · 390 employees at the site · Closed Nov 17, 1983

Station Hwy 69, La Cygne, KS 66040 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 217556463 OPENED AUG 17, 1981Closed

Complaint · Partial · Safety · 365 employees at the site · Closed Sep 21, 1981

La Cygne Generating Station, La Cygne, KS 66040 · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.23(a)(2) · Guarding floor and wall openings and holes
Other-than-serious$0$0Aug 31, 1981Closed

Inspection 217494913 OPENED JUL 1, 1981Closed

Accident · Complete · Safety · 3 employees at the site · Closed Aug 11, 1981

5501 Aberdeen, Fairway, KS 66205 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 217522721 OPENED DEC 4, 1980Closed

Accident · Partial · Safety · 2,865 employees at the site · Closed Dec 19, 1980

150 Terrace At 151st St, Olathe, KS 66061 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 217519982 OPENED JUN 19, 1978Closed

Complaint · Complete · Safety · 320 employees at the site · Closed Mar 10, 1984

5 Mile East On Highway 65 Of, La Cygne, KS 66040 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Inspection 217519925 OPENED MAY 24, 1978Closed

Complaint · Complete · Safety · 323 employees at the site · Closed Jun 16, 1978

Us Highway 69, La Cygne, KS 66040 · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1 Other-than-serious$0$0May 30, 1978Closed
Citation 1, item 2
29 CFR 1910.243(c)(5)(i) · Guarding of portable powered tools
Other-than-serious$0$0May 30, 1978Closed

Inspection 217533389 OPENED JUL 20, 1977Closed

Complaint · Partial · Health · 2,600 employees at the site · Closed Mar 10, 1984

Box 211, La Cygne, KS 66040 · OSHA's record · Phone and website on Google Maps

No citations from this inspection.

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2018, the Lenexa site logged 2 recordable injuries or illnesses among about 87 workers: 1.9 per 100 full-time workers, against a median of 1.0 for its industry. Those cases cost 5 days away from work.

Site and yearWorkersCasesDays-away casesRateIndustry median
KCP&L - Johnson County Service Center
Lenexa · 2018
87 211.91.0
KCP&L - Spearville Wind Energy Facility
Spearville · 2018
7 000.01.0

Included with any plan: 4 more yearly logs from these sites, back to 2016, with each site's average rate over its latest three years. Already a subscriber? Sign in.

See plans

Severe injury reports

Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 1 report on file.

Mar 22, 2019, Spearville: Hospitalization · intracranial injuries, unspecified · brain

On Friday, March 22, 2019, two employees were lowering material in a wind turbine after repairing a turbine motor. A 6-foot-long tool fell from more than 90 feet up, striking an employee on the ground and causing head trauma.

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.184 · Slings

29 CFR 1910.184(d)

(d) Inspections. Each day before being used, the sling and all fastenings and attachments shall be inspected for damage or defects by a competent person designated by the employer. Additional inspections shall be performed during sling use, where service conditions warrant. Damaged or defective slings shall be immediately removed from service.

29 CFR 1910.23 · Guarding floor and wall openings and holes

29 CFR 1910.243 · Guarding of portable powered tools

29 CFR 1910.243(c)(5)(i)

(5) Mounting and inspection of abrasive wheels. (i) Immediately before mounting, all wheels shall be closely inspected and sounded by the user (ring test, see subpart O, § 1910.215(d)(1)) to make sure they have not been damaged in transit, storage, or otherwise. The spindle speed of the machine shall be checked before mounting of the wheel to be certain that it does not exceed the maximum operating speed marked on the wheel.

29 CFR 1926.950 · Electric Power Transmission and Distribution: general

29 CFR 1926.950(b)(2)

(2) Qualified employees. Each qualified employee shall also be trained and competent in:

OSH Act Section 5 · General Duty Clause

Other fossil fuel electric power generation employers in Kansas

Alert subscribers get notified of each newly cited employer in Kansas the morning it is posted. See the alert plans.

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.