OSHA SearchOSHA records by employer

Southeast Power Corporation Western: OSHA inspections and violations

Marion, Texas · Wind Electric Power Generation · NAICS 221115

1inspections
3citation items
$34,755current penalties
Oct 23, 2025last inspection

OSHA inspectors have visited Southeast Power Corporation Western in Texas one time.

It opened on Oct 23, 2025 as part of a related case, in Marion and is still open.

In all, OSHA issued 3 citation items: 3 serious.

The penalties, $34,755 in total, stand where OSHA first set them.

The rule cited most here is 1926.960 (working on or near exposed energized parts), 3 times.

Among utility employers, the typical cited inspection since 2015 ends with a $0 penalty. Southeast Power Corporation Western averages $34,755 across 1 cited inspection.

Southeast Power Corporation Western: OSHA citation items per year, 2025 to 2025
Citation items per year, by inspection date.

Texas · latest 90 days of OSHA records

394employers cited

Get notified the morning OSHA posts each new citation in Texas: the employer, the site address, the rules broken and the penalty.

See who gets cited next

Latest cited in Texas

Checking a subcontractor, a client or your own company? Watch Southeast Power Corporation Western and get notified the morning OSHA posts a new citation for it.

Watch this company

Inspection history

Inspection 348569229 OPENED OCT 23, 2025Open

Unprogrammed related · Partial · Safety · 1 employee at the site · Open

Tower 130 Near 302 East Krueger Street, Marion, TX 78124 · Wind Electric Power Generation · OSHA's record · Phone and website on Google Maps

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1926.960(b)(1)(i) · Working on or near exposed energized parts
Serious$11,585$11,585Apr 23, 2026Contested
Citation 1, item 2
29 CFR 1926.960(c)(1)(i) · Working on or near exposed energized parts
Serious$11,585$11,585Apr 23, 2026Contested
Citation 1, item 3
29 CFR 1926.960(c)(1)(ii) · Working on or near exposed energized parts
Serious$11,585$11,585Apr 23, 2026Contested

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1926.960 · Working on or near exposed energized parts

29 CFR 1926.960(b)(1)(i)

(b) General—(1) Qualified employees only. (i) Only qualified employees may work on or with exposed energized lines or parts of equipment.

29 CFR 1926.960(c)(1)(i)

(c) Live work—(1) Minimum approach distances. (i) The employer shall establish minimum approach distances no less than the distances computed by Table V-2 for ac systems or Table V-7 for dc systems.

29 CFR 1926.960(c)(1)(ii)

(ii) No later than April 1, 2015, for voltages over 72.5 kilovolts, the employer shall determine the maximum anticipated per-unit transient overvoltage, phase-to-ground, through an engineering analysis or assume a maximum anticipated per-unit transient overvoltage, phase-to-ground, in accordance with Table V-8. When the employer uses portable protective gaps to control the maximum transient overvoltage, the value of the maximum anticipated per-unit transient overvoltage, phase-to-ground, must provide for five standard deviations between the statistical sparkover voltage of the gap and the statistical withstand voltage corresponding to the electrical component of the minimum approach distance. The employer shall make any engineering analysis conducted to determine maximum anticipated per-unit transient overvoltage available upon request to employees and to the Assistant Secretary or desig

Other wind electric power generation employers in Texas