OSHA SearchOSHA records by employer

Volt Power, LLC: OSHA inspections and violations

Dallas, Texas · Electric Power Distribution · NAICS 221122

2inspections
6citation items
$434,314current penalties
Jul 16, 2021last inspection

Since 2018, OSHA inspectors have visited Volt Power, LLC in Texas 2 times.

The most recent inspection opened on Jul 16, 2021 after a fatality or catastrophe, in Montgomery.

In all, OSHA issued 6 citation items: 6 serious.

The proposed penalties came to $437,967; today they stand at $434,314, 1% less.

The rule cited most here is 1910.269 (electric power generation, transmission, and distribution), 4 times.

Among utility employers, the typical cited inspection since 2015 ends with a $0 penalty. Volt Power, LLC averages $217,157 across 2 cited inspections.

2 inspections on this page followed a fatal incident.

Volt Power, LLC also files yearly injury logs with OSHA, summarized below.

Volt Power, LLC: OSHA citation items per year, 2018 to 2021
Citation items per year, by inspection date.

Want to know if OSHA cites Volt Power, LLC again? Add it to a watchlist and we will email you the morning the citation shows up.

Watch this company

Inspection history

Inspection 345422620 OPENED JUL 16, 2021Closed

Fatality or catastrophe · Partial · Safety · 8 employees at the site · Closed Sep 26, 2022

600 Margaritaville Parkway, Montgomery, TX 77356 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Jul 15, 2021 (fatal): Employee is killed after cutting energized high voltage line

At 2:30 p.m. on July 15, 2021, an employee was cutting a 34,500 volt high voltage underground power line. The power to the phase being cut had not been deenergized which caused an arc flash. The employee was killed after he was electrocuted and electrically burned on the hands and face.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 2
29 CFR 1926.961(c)(6) · Deenergizing lines and equipment for employee protection
Serious$13,653$10,000Dec 2, 2021Final

Inspection 343630026 OPENED NOV 28, 2018Closed

Fatality or catastrophe · Complete · Safety · 5 employees at the site · Closed Jun 14, 2022

1054 N. St. Augustine, Dallas, TX 75217 · Electric Power Distribution · OSHA's record · Phone and website on Google Maps

Incident on Nov 27, 2018 (fatal): Employee is electrocuted while guiding power pole into groun

At 4:30 p.m. on November 27, 2018, an employee was guiding a power pole into the ground. The power pole became energized, resulting in an electrical shock. The employee was killed.

Citation and ruleTypeProposedCurrentIssuedStatus
Citation 1, item 1
29 CFR 1910.269(q)(1)(iii) · Electric power generation, transmission, and distribution
Serious$13,260$13,260May 22, 2019Final
Citation 1, item 2
29 CFR 1910.137(c)(2)(viii) · Electrical protective equipment
Serious$13,260$13,260May 22, 2019Final
Citation 2, item 1
29 CFR 1910.269(a)(2)(i)(a) · Electric power generation, transmission, and distribution
Serious$132,598$132,598May 22, 2019Final
Citation 2, item 2
29 CFR 1910.269(p)(4)(i) · Electric power generation, transmission, and distribution
Serious$132,598$132,598May 22, 2019Final
Citation 2, item 3
29 CFR 1910.269(p)(4)(iii)(a) · Electric power generation, transmission, and distribution
Serious$132,598$132,598May 22, 2019Final

Injury and illness logs

From the Form 300A summaries employers file with OSHA each year. Rate = recordable cases per 100 full-time workers.

In 2020, the Dallas site logged 7 recordable injuries or illnesses among about 187 workers: 3.0 per 100 full-time workers, against a median of 1.0 for its industry. Those cases cost 185 days away from work.

Site and yearWorkersCasesDays-away casesRateIndustry median
Volt Power Dallas Office
Dallas · 2020
187 723.01.0

The rules behind these citations

Current text from the Code of Federal Regulations. Some citations were issued under older wording.

29 CFR 1910.137 · Electrical protective equipment

29 CFR 1910.137(c)(2)(viii)

(viii) Electrical protective equipment shall be subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table I-4 and Table I-5.

29 CFR 1910.269 · Electric power generation, transmission, and distribution

29 CFR 1910.269(a)(2)(i)(a)

(A) Each employee shall be trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments.

29 CFR 1910.269(p)(4)(i)

(4) Operations near energized lines or equipment. (i) Mechanical equipment shall be operated so that the minimum approach distances, established by the employer under paragraph (l)(3)(i) of this section, are maintained from exposed energized lines and equipment. However, the insulated portion of an aerial lift operated by a qualified employee in the lift is exempt from this requirement if the applicable minimum approach distance is maintained between the uninsulated portions of the aerial lift and exposed objects having a different electrical potential.

29 CFR 1926.961 · Deenergizing lines and equipment for employee protection

Other electric power distribution employers in Texas

Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.