Wisconsin Electric Power Company: OSHA inspections and violations
Milwaukee, Wisconsin · Fossil Fuel Electric Power Generation · NAICS 221112
39inspections
28citation items
$33,675current penalties
May 1, 2026last inspection
Since 1973, OSHA inspectors have visited Wisconsin Electric Power Company in Wisconsin 39 times.
The most recent inspection opened on May 1, 2026 after a fatality or catastrophe, in East Troy.
In all, OSHA issued 28 citation items: 11 serious and 17 other-than-serious.
The proposed penalties came to $35,765; today they stand at $33,675, 6% less.
The rule cited most here is 1910.1027 (cadmium), 3 times.
Among utility employers, the typical cited inspection since 2015 ends with a $0 penalty. Wisconsin Electric Power Company averages $13,260 across 1 cited inspection.
6 inspections on this page followed a fatal incident.
It reported 3 severe injuries to OSHA since 2015.
Citation items per year, by inspection date.
Wisconsin · latest 90 days of OSHA records
218employers cited
Get notified the morning OSHA posts each new citation in Wisconsin: the employer, the site address, the rules broken and the penalty.
Checking a subcontractor, a client or your own company? Watch Wisconsin Electric Power Company and get notified the morning OSHA posts a new citation for it.
Incident on Aug 14, 2003 (fatal): Employee is electrocuted when boom contact utility line
At approximately 2:15 p.m. on August 14, 2003, a crew of three was tasked with s etting a new electrical utility pole that was intended to eventually raise the o verhead electrical utility line from the current height position. The hole for t he pole was first dug using the auger attached to the boom of the truck. Once th e hole was dug, the new utility pole was picked up by attaching a steel link cha in sling around the pole and attached to a hook that was lowered from the boom t ruck nylon rope. The pole was lifted between the east primary wire, 4.8kv phase to ground, and the center neutral. The pole was set and dirt was back-filled and tampered into place using a hydraulic tamper. Two crew members were accomplishi ng shoveling of dirt into the hole and tamping of the back-filled dirt. The boom operator at this time was attempting to disengage the steel chain sling from th e pole that had hung up on the pole. In an attempt to release the sling, the ope rator lowered the boom so that the sling would release. As the boom was lowered, the hydraulic hoses that are strengthened with steel coil came into contact wit h the east primary energizing the boom truck and subsequently the hydraulic tamp er being operated by a crew member electrocuting him.
Incident on Feb 12, 1995 (fatal): Burn - steam pipe rupture
A feed water inlet header pipe supplying a boiler at an electric power generatin g station ruptured at elevation 227. (The elevations noted in the abstract are i n reference to Lake Michigan which is at a relative elevation of 0. Ground eleva tion at the plant was 105.) The pipe was under 1875 psi, and the contained steam was at 426 degrees Fahrenheit at the time of release. The rupture flooded the u pper portion of a generation unit at the generating plant. Two supervisory emplo yees, who were performing a routine inspection, were trapped in the area at elev ation 303. One of the employees died at the scene; he had burns over 90 percent of his body. The second employee suffered burns over 60 percent of his body. He was hospitalized in critical condition. (A technical team was to conduct a failu re analysis, including metallurgical evaluation of the 15-year-old pipe, after t he accident. The employer's quality assurance program for determining serviceabi lity did not include this external boiler piping system as it was not deemed a h igh-risk area.)
No citations from this inspection.
Inspection 122041973 OPENED JUL 22, 1994Closed
Accident · Partial · Safety · 3 employees at the site · Closed Sep 6, 1994
Incident on Jul 22, 1994 (fatal): Electric shock - direct contact with overhead line
An underground transformer supplying service for a residential complex had been repaired. A troubleshooter with 42 years of experience was dispatched to reenerg ize the line supplying the transformer. The employee was working from a utility pole at the primary (4800-volt) level. There were two parallel lines, an east an d a west, descending the pole at this point. Only the west line was deenergized; the east line remained energized. The employee was to remove the three groundin g jumpers from the pothead stirrups located on the lower crossarm and then from the grounding bracket on the other side of this crossarm. Then he was to reenerg ize the west line. The employee positioned himself on the south side of the pole --he was facing north with the energized east potheads to his right. The horizon tal distance between the grounding bracket and the nearest energized pothead was about 400 millimeters. The employee had removed the three grounding jumpers fro m the west potheads and had started to remove the jumpers from the grounding bra cket. He was using metal pliers and leather wristlet gloves for this purpose. (H e was not wearing rubber insulating gloves, nor were the energized east potheads or lines covered with rubber insulating equipment.) The employee contacted an e nergized east pothead with his right forearm while his right hand was touching t he grounding bracket. The employee was electrocuted.
No citations from this inspection.
Inspection 103525549 OPENED SEP 17, 1993Closed
Accident · Partial · Safety · 1 employee at the site · Closed Sep 30, 1993
Incident on Sep 17, 1993 (fatal): Employee dies of heart attack after fall into pool
A meter reader for an electric utility fell into an indoor pool at a hotel and d ied from a heart attack while in the pool. The deep end of the pool was about 1. 2 meters straight ahead through the entrance door. A fixed pool ladder extended into the path of travel to the utility room, where the meter was located. Lack o f illumination was probably a contributing factor to the accident. The area ligh ts were off and the illumination was between 1 and 2 lux per square meter. The e xit lights were also burned out. It could not be determined if the fall preceded the heart attack.
No citations from this inspection.
Inspection 102984788 OPENED SEP 14, 1992Closed
Referral · Partial · Safety · 60 employees at the site · Closed Jan 20, 1993
Incident on May 31, 1990 (fatal): Struck against material - medical complications
AN 38-YEAR-OLD EMPLOYEE OF AN ELECTRIC UTILITY COMPANY WAS CLEANING AND ORGANIZI NG A SMALL STORAGE AREA. THE STORAGE AREA WAS 8 FEET WIDE, 8 FEET HIGH, AND 15 F EET WIDE. THE EMPLOYEE FAINTED AND FELL AGAINST THE HANDLE OF A STORED HYDRAULIC POWER UNIT. HE DID NOT REPORT THE INCIDENT UNTIL 2 DAYS LATER, WHEN HE BEGAN TO EXPERIENCE SOME DISCOMFORT. THE EMPLOYEE ENTERED THE HOSPITAL AND SUFFERED A SE RIES OF COMPLICATIONS, INCLUDING AN ABSCESS, INFECTION, DROP IN BLOOD PRESSURE, AMPUTATION OF EXTREMITIES FROM GANGRENE, SKIN SLOUGHING, AND MULTIPLE ORGAN FAIL URES. THE EMPLOYEE DIED ON JULY 14, 1990. NO CAUSAL FACTORS WERE IDENTIFIED FOR THE EMPLOYEE'S SYMPTOMS.
No citations from this inspection.
Inspection 103046967 OPENED DEC 12, 1989Closed
Referral · Partial · Safety · 300 employees at the site · Closed Apr 2, 1990
Incident on Dec 12, 1989: Burn - release of steam during maintenance
TWO MAINTENANCE MEN AT AN ELECTRIC POWER GENERATION PLANT REMOVED A CHECK VALVE COVER FROM A STEAM SYSTEM. THE SECTION OF THE STEAM LINE WAS ISOLATED AND TAGGED , BUT IT COULD NOT BE VENTED OR DRAINED FIRST. THE SECTION WAS ONLY PARTIALLY DE PRESSURIZED WHEN THE COVER WAS LOOSENED. WHEN THE EMPLOYEES REMOVED ALL FASTENER S HOLDING THE COVER IN PLACE, IT BLEW OFF, AND THE STEAM LINE SPRAYED THE TWO EM PLOYEES WITH STEAM AND HOT WATER. THE EMPLOYEES WERE WEARING SAFETY GLASSES AND WORK GLOVES, BUT WERE NOT USING ANY OTHER SHIELDING OR PROTECTIVE CLOTHING. THE EMPLOYEES RECEIVED SECOND DEGREE BURNS OVER 20 PERCENT OF THEIR BODIES.
Citation and rule
Type
Proposed
Current
Issued
Status
Citation 1, item 1
29 CFR 1910.132(a) · Personal protective equipment, general requirements
Employers must report any work-related amputation, in-patient hospitalization or loss of an eye to OSHA within 24 hours. 3 reports on file.
Dec 8, 2021, Milwaukee: Amputation · amputations · fingertip(s)
An employee was using a pneumatic torque wrench to rotate a bearing bolt on a bucket truck when the wrench slipped and the employee's finger was caught between the lever and a steel pedestal, resulting in a fingertip amputation.
Feb 17, 2021, Oak Creek: Hospitalization · crushing injuries · finger(s), fingernail(s), unspecified
An employee was working at a rail switching location when he slipped and his thumb was crushed between two rails.
Sep 1, 2017, Pleasant Prairie: Amputation · amputations · fingertip(s)
On September 1, 2017, an employee was standing and waiting for a silo to empty when a piece of angle iron fell from above and struck the employee's hand, amputating the thumb tip.
The rules behind these citations
Current text from the Code of Federal Regulations. Some citations were issued under older wording.
29 CFR 1904.2 · Partial exemption for establishments in certain industries
(iii) Eight-hour TWA exposures shall be determined for each employee on the basis of one or more personal breathing zone air samples reflecting full shift exposure on each shift, for each job classification, in each work area. Where several employees perform the same job tasks, in the same job classification, on the same shift, in the same work area, and the length, duration, and level of cadmium exposures are similar, an employer may sample a representative fraction of the employees instead of all employees in order to meet this requirement. In representative sampling, the employer shall sample the employee(s) expected to have the highest cadmium exposures.
29 CFR 1910.1027(k)(7)
(7) Waste, scrap, debris, bags, containers, personal protective equipment, and clothing contaminated with cadmium and consigned for disposal shall be collected and disposed of in sealed impermeable bags or other closed, impermeable containers. These bags and containers shall be labeled in accordance with paragraph (m) of this section.
29 CFR 1910.1027(m)(4)(i)
(4) Employee information and training. (i) The employer shall train each employee who is potentially exposed to cadmium in accordance with the requirements of this section. The employer shall institute a training program, ensure employee participation in the program, and maintain a record of the contents of such program.
Alert subscribers get notified of each newly cited employer in Wisconsin the morning it is posted. See the alert plans.
Source: U.S. Department of Labor, OSHA enforcement data. A citation is OSHA's allegation; employers can contest it, and the status column shows where each item stands. Something wrong on this page? Tell us.